Enertech SK040 series Скачать руководство пользователя страница 5

5

SK Models IOM

Enertech Global

Consumer Instructions:

The dealer should instruct the consumer in proper 

operation and maintenance of the unit, as well as 

giving them an overview of the indictor lights on the 

control board.  Also, provide the consumer with the 

manufacturer’s Owner’s Manual for the equipment 

being installed.  

Enertech Global D-I-Y Policy:

Enertech Global’s products may include electrical, 

refrigerant and/or water connections.  Federal, 

state and local codes and regulations apply to 

various aspects of the installation.  Improperly 

installed equipment can lead to equipment failure 

and health/safety concerns.  For these reasons, 

only qualified technicians should install an Enertech 

Global product.  Enertech Global does not sell 

equipment directly to homeowners.  Internet 

Websites and HVAC outlets may allow for the 

purchases directly by the homeowners and do-it-

yourselfers, but Enertech Global offers no warranty 

on equipment that is purchased via the internet or 

installed by persons without proper training.  

Electrical:

All wiring, line and low voltage, should comply with 

the manufacturer’s recommendations, The National 

Electrical Code, and all other local codes and 

ordinances.  

Unit Placement:

Special care should be taken in locating the unit.  

Try to select an exterior wall away from common 

living areas, bedrooms, family rooms, etc.  The unit 

must be installed greater than 16 inches from any 

exterior wall, and 32 inches from any other device.  

Air flow should be directed away from the structure 

with a minimum 5 foot clearance area. See below.

 

Climate & Flow:

The flow requirements must be verified by the 

installer for each specific application. It is also 

important for the installer to pay attention to

 

the 

local climate conditions. If it is determined that the 

loop temperature will drop below 23°F (most likely 

to occur during the winter months in some areas 

of the United States or Canada), then the unit must 

be bypassed, and the system must be completely 

drained.

Other Installation Considerations:

The SK Series unit does not come with the 

mounting legs or the pipe protector installed.  They 

are shipped in separate boxes on top of, or inside, 

the unit.

Installing the Mounting Legs:

1.  Flip the unit over to gain access to the mounting 

holes on the bottom of the unit.  It is best to do this 

with two people. The unit should be flipped over on 

to a blanket, piece of cardboard, etc., in order to 

protect the unit from damage.  

2.  Take the (4 or 6) 5/16-18 x ¾” bolts provided with 

the legs, and use them to attach the legs to the 

unit.  The *SK040 unit has (2) mounting legs, but 

the *SK060 has a total of (3). See Figure #1 and #2 

below for details.

Figure #1

Figure #2

Note: *SK060 Model will have (3) legs

Once the unit install is completed, the pipe 

protector will need to be attached to the unit.

Installing the Pipe Protector:

1.  Remove the side door from the unit.  This will 

expose the horizontal bracket that the bottom 

tabs of the door/pipe protector slip into.  See

 

Figure #3.

SECTION 3: INSTALLATION CONSIDERATIONS

Содержание SK040 series

Страница 1: ...Installation OperationsManual SK SERIES DRY FLUID COOLER REVISION REV A 20D201 01NN 20D201 01NN...

Страница 2: ...ector 6 SECTION 4 PRINCIPLES OF OPERATIONS Outdoor Air Operation 7 Hybrid Operation 7 SECTION 5 UNIT DATA INFORMATION Unit Physical Data 7 Unit Electrical Data 7 Unit Dimensional Data 8 SECTION 6 CONT...

Страница 3: ...Inspection Upon receipt of any geothermal equipment carefully check the shipment against the packing slip and the freight company bill of lading Verify that all units and packages have been received...

Страница 4: ...te Preparation Survey the installation site to determine the best location for placing the outdoor unit When possible select an exterior wall away from common living areas bedrooms family rooms etc Gr...

Страница 5: ...m any exterior wall and 32 inches from any other device Air flow should be directed away from the structure with a minimum 5 foot clearance area See below Climate Flow The flow requirements must be ve...

Страница 6: ...de of the pipe protector will sit behind the flange of the bottom pan 5 Use the two screws that were removed with the horizontal bracket to attach the top flange of the pipe protector in the same loca...

Страница 7: ...60 216 252 Fan Motor FLA Int Loop Pump FLA Total Unit FLA Min Circuit AMPS Max Fuse HACR SK040 SK060 Model Voltage Code Fan Option 60 Hz Power Outdoor Air Operation vs Hybrid Operation As stated earli...

Страница 8: ...W 46 5 22 0 24 3 29 1 4 0 6 4 3 7 4 3 38 5 23 7 8 3 5 0 2 1 POWER SUPPLY CONNECTION LOW VOLTAGE CONNECTION SOURCE WATER OUT SOURCE WATER IN SK060 Models 63 5 22 7 5 1 2 3 LOW VOLTAGE CONNECTION POWER...

Страница 9: ...circuit board When the fan is off this input is open When the fan is running in normal operation the fan alarm output is closed If the fan alarm output is open for 30 continuous seconds while the fan...

Страница 10: ...cording to the same logic as Option 1 It will also automatically perform loop cooling according to the temperature logic described in Option 2 Loop cooling is active when both of the following conditi...

Страница 11: ...X SLOW FLASH FLASH X X X FAST FLASH FLASH X SLOW FLASH X X FLASH X DIP SWITCH OPTION SELECTED 1 2 3 4 2 OPTION 1 LOOP PUMP OFF OFF OFF OPTION 2 LOOP PUMP ON OFF OFF OPTION 3 LOOP PUMP OFF ON OFF OPTI...

Страница 12: ...12 Enertech Global SK Models IOM SECTION 7 WIRING DIAGRAMS Models with Internal Loop Pump Models with Flow Switch...

Страница 13: ...Temp 3 BTUH CFM o F o F GPM o F o F o F 51 600 3 500 70 14 15 85 7 8 67 600 3 500 70 18 15 90 9 11 82 300 3 500 70 22 15 95 11 14 49 700 3 500 90 13 15 105 7 8 65 700 3 500 90 17 15 110 9 11 80 800 3...

Страница 14: ...m submitter Ifdifferent than company OTHER NOTES _______________________________________________________________________________ _______________________________________________________________________...

Страница 15: ...______________________________________________________________________ City _____________________________State Prov __________ Email ___________________________________________ Application Residential...

Страница 16: ...h product may change without notice and may not be as described herein For the most up to date information please visit our website or contact our Customer Service department at info enertechgeo com S...