ADJUSTMENT OF BURNER

The burner is from the factory pre-set
to an average value that must then be
adjusted to the boiler in question.
All burner adjustments must be made
in accordance with boiler manu-
facturers instructions.These must
include the checking of flue gas tempe-
ratures, average water temperature and
CO

2

 or O

2

 concentration

GENERAL INSTRUCTIONS

The installation of the gas burner must
be carried out in accordance with cur-
rent regulations and standards. The
installers of gas burners should therfo-
re be acquainted with all regulations
and  ensure that the installation comp-
lies with the requirements. The instal-
lation, mounting and adjustment should
be  made with the greatest care and
only the correct gas should be used.

OPERATING INSTRUCTIONS

The operating instructions accompa-
nying the burner should be left in a
prominent position in the boiler room.

INSTRUCTIONS

The user should be thoroughly instruc-
ted in the function of the gas burner and
the whole installation. The supplier
must instruct the user.

INSPECTION AND MAINTENANCE

Daily inspection is advisable.

SERVICE

Service should only be carried out by
qualified personell. Replacement parts
should be of the same make and appro-
ved by the same authorities as the
original. If the burner is converted to fire
another gas quality it must be re-
commissioned. If town gas is to be
fired the combustion head must be
converted and the  gas train adjusted to
suit, (e.g.a larger gas armature or a
different spring in the governor may be
required).

START UP

After the burner has been fitted to the
boiler and the electric connection, the
leakage control, the venting and the
electric function test have been carried
out, the burner will be ready for start-
up.

Hower, study the sections dealing with
adjustments of  multi-bloc, combu-
stion air and combustion head.

172 305 52  05-01

GENERAL INSTRUCTIONS

Open the ball valve and switch on the
main switch. If the burner starts the
actual adjustment can be made.

AIR ADJUSTMENT

On all burners the air adjustment can
be made with or without the cover
fitted. Final fine adjustment must be
made with the cover on.

ADJUSTMENT OF BURNER HEAD

The burners are equipped with an ad-
justment device changing the position
of the brake plate in the burner head.
This is used to adjust the correct pres-
sure drop over the combustion device
and thereby obtain a good pulsation
free combustion.

Which position to use depends on
input and overpressure in the boiler.

A general rule is that the lower capaci-
ty the smaller the opening between
brake plate and combustion device.

ADJUSTMENT OF BRAKE PLATE

-

Turn by means of an allen key the
screw in the desired direction.

STG120/1, STG120/2, STG146/1

-

To reduce the opening: turn the
screw to the left.

-

To increase the opening: turn the
screw to the right.

STG146/2

-

To reduce the opening: turn the
screw to the right.

-

To increase the opening: turn the
screw to the left.

Gas quality

CO

2

%

0

2

%

max CO

2

%

lambda 1,2

Natural gas

10,0

3,5

11,9

LPG

11,5

3,5

13,9

The adjustment of the position of the
brake plate affects the air flow. It is
therefore always necessary to make a
fine adjustment of the air by means of
the adjustment device of the burner.

CONTROL OF BURNER HEAD

To check the burner head, brake plate
and electrodes proceed as follows:
Remove the cover. Loosen the union
nut between inner assembly and multi-
bloc. Loosen the burner from the flange
and withdraw the burner from the boi-
ler. If it is necessary to remove the
burner tube, loosen the two allen
screws, turn and withdraw the burner
tube.

COMMISSIONING OF INSTALLA-
TION

Control of the combustion. The com-
bustion quality is checked by means of
a flue gas analysis device. Adjust the
burner to appr. 20% excess air in
accordance with the table. Check the
flue gas temperature. Calculate the
efficiency. Check also the actual gas
volume on the  gas meter so that the
correct input is achieved.

Содержание Bentone STG 146

Страница 1: ...Providing sustainable energy solutions worldwide 178 040 26 Installation and maintenance instruction STG 146...

Страница 2: ......

Страница 3: ...tiBloc 6 Ionisationelectrode 7 Inner assembly 8 Brakeplate 9 Burner tube 10 Ignition electrode 11 Air damper 12 Front part fan housing 13 Rear part fan housing 14 Air pressure switch 15 Shieldingarran...

Страница 4: ...0V Ampl 1 Calorific value Natural gas 10 kWh Nm3 2 Depending on gas quality and availablepressure Type Capacity Nm3 h at min Nm3 h at max Ratedinletpressures kW output of burner 1 output of burner 1 m...

Страница 5: ...m3 LPG 26 kWh Nm3 2 Depending on gas quality and availablepressure Type Capacity Nm3 h at min Nm3 h at max Ratedinletpressures kW output of burner 1 output of burner 1 mbar Naturalgas LPG Naturalgas L...

Страница 6: ...TECHNICAL DATA 172 215 45 98 01 DIMENSIONS OF FLANGE Flange 10 145 0 23 5 109 5...

Страница 7: ...witch mini 5b Gas pressure switch maxi 6a Mainvalve Incorporated in the Multibloc 6b Safetyvalve 1 7 Valveprovingsystem 9 Air pressure switch 10 Gas burner control Pos 5b 7 Components not required acc...

Страница 8: ...ction in any other direction thearmaturecanbeturned180 tothe left and upwards It is also possible to connectthegastothemulti blocstraight backwards The armature can also be extended so that it comes o...

Страница 9: ...Air pressure switch S9 Gas pressure switch T1 Ignitiontransformer X1 Plug in contact burner X2 Plug in contact boiler Y1 Gassolenoidvalve If there is no plug in contact X2 on the boiler connect to th...

Страница 10: ...programme If premature flame signal at start of pre purge time Immediate lock out If contacts of air pressure switch LP have welded during tw No start If no air pressure signal Lock out when t10 has...

Страница 11: ...ot open or extraneous light on burner startup LP faulty LP incorrectly adjusted 5 x Extraneous light during pre purging Or internal device fault 7 x Loss of flame during operation Poor adjustment of b...

Страница 12: ...up Green Red Undervoltage Yellow Red Disruption alarm Red Flashing code for fault codes Flashingred Interfacediagnostics Redflickering Continuous Off Red Yellow Green 1 2 Limit on start attempts LME11...

Страница 13: ...5 3 s Interfacediagnostics Connecting signal amplifier 2 2 Red flashing code on Possible causes signal lamp LED Flashing 2 x No flame at End of TSA Defectiveorobscuredflamemonitor Defectiveorobscured...

Страница 14: ...e shouldbeclosed Connectapressure gauge to the test nipple Pa see fig Thetestpressureinthesystemshould be 1 5x max inlet pressure or min 150 mbar If any leakage locate the source by means of soapy wat...

Страница 15: ...MEASURES AND CHECKS BEFORE START UP INNER ASSEMBLY Town gas not CE approved INNER ASSEMBLY Natural gas LPG INNER ASSEMBLY Biogas UV detector Natural gas 2 5 8 2 5 8 172 205 77 07 01...

Страница 16: ...essure of the gas at the gas meter 15 0 mbar f f 1 11 The gas volume read on the gas meter actually reads 1 11 12 9 14 4 m3 h Net calorific value Gasquality kWh Nm3 kJ Nm3 kcal Nm3 Naturalgas 10 3 37...

Страница 17: ...e for supply pressu re after the filter 1 Test nipple for supply pressure 2 Coils electrical connection 3 Gas filter 4 Test nipple for governor pressure 5 Test nipple for burner pressure 10 Screws for...

Страница 18: ...tofthegovernorpressu re can be made on the adjustment screw 11 bymeansofanAllenkey size 2 mm Adjustmentclockwisegivesahigher pressure Adjustment anti clockwise gives a lowerpressure CHECK OF FILTER Sc...

Страница 19: ...INSTRUCTIONS Open the ball valve and switch on the main switch If the burner starts the actual adjustment can be made AIRADJUSTMENT On all burners the air adjustment can be made with or without the co...

Страница 20: ...172 305 50 97 01 GENERAL INSTRUCTIONS CONTROL OF BURNER HEAD AIRADJUSTMENT ADJUSTMENT OF INNER ASSEM BLY...

Страница 21: ...ichthegasswitchshouldswitchoff Set this pressure by means of the valve Carefully turn the knob see figure until the gas pressure switch switches off The value shown on the scale should then approximat...

Страница 22: ...Troublefreeoperationisdependenton three factors electricity gas and air supply Should there be any changes intheratiobetweenthesethreefactors there is a risk of break downs It has beenprovedthatmostbr...

Страница 23: ...cient 5 Is the gas relay of the burner ready for start and not lockedout 6 Is the air supply to the burner sufficient To facilitate fault location we have drawn up a scheme showing the most frequent f...

Страница 24: ...on the secondary side The ignition cable and the ionisation cable have been transposed Noflameestablishmentinspiteofatroublefreestart Thegassolenoidvalvedefective The gas solenoid valve does not open...

Страница 25: ...cell is in a wrong position Voltage drop at certain times Air pressure switch defective or incorrectly adjusted Spark over in ignition electrodes REMEDY Contact the electricity authorities Adjusttheig...

Страница 26: ...ply Insulate the chimney CAUSE The ambient temperature of the gas relay is too high The ignition spark is too weak Badcombustion Bad draught conditions The flue gas temperature is too high The CO2 con...

Страница 27: ...le marquage CE de conformit Ljungby Sweden 141127 27 11 14 ENERTECH AB Bentone Division Box 309 SE 341 26 Ljungby Sweden H kan Lennartsson Enertech AB declares that the above mentioned products compl...

Страница 28: ......

Страница 29: ...ample room ther mostat if any 4 Check that the gas pressure to the burner is sufficient 5 Check that the electric fuses have not blown 6 Make a new attempt to start the burner and check the counter of...

Страница 30: ...Measure ment Before After C A mbar mbar Small flame Large flame Measures Date Nm3 gas h Governor CO2 CO Flue gas temp Ionisa tion current Pressure Efficiency Fire room Chimney Measure ment Before Aft...

Страница 31: ......

Страница 32: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: