background image

OUTPUT RANGE AND NOZZLES RECOMMENDED

Oil capacity

Output

Recommended nozzle

Recommended

kg/h

kW

Mcal/h

Angle

Danfoss Monarch

Pump pressure

60-2 ø 130

20,0-63,0

237-747

204-642

45° - 60°

S, B

R, PLP

14 bar

60-2 ø 120

35,0-75,0

415-889

357-765

45° - 60°

S, B

R, PLP

14 bar

60-2 ø 110

40,0-90,0

474-1067

408-918

45° - 60°

S, B

R, PLP

14 bar

TECHNICAL DATA

Type designation B 60-2

DIMENSIONS

Length of

Flange

 burner tube

Measure B

Burner head Standard

290

260

Burner head Long design

390

360

595

290

ø

1

5

5

ø

1

5

8

B

610

3

2

1

4

0

0

4

0

5

171 215 78  00-02

BURNER HEAD
Brake plate ø130

The net calorific value of 11,86 kWh/kg for light oil has been used.

RECOMMENDED NOZZLE

Because of different boiler types
existing on the market, with varying
combustion chamber designs, it is not
possible to state a definite spray angle
or spray pattern.

Note that the spray angle and the spray
pattern change with the pump pressure.

RECOMMENDED PUMP PRESSURE

Recommended pump pressure 14 bar.

10,0-13,0

3,5-4,0

2,0-3,0

7,0-9,0

Содержание Bentone B60-2FH

Страница 1: ...Providing sustainable energy solutions worldwide 178 039 61 2 2016 11 28 Installation and maintenance instruction B60 2FH...

Страница 2: ......

Страница 3: ...ing lamp Stage 2 13 Cover inspectionglass 14 Indicating lamp Stage 1 15 Switch 0 l 16 Fanwheel 17 Electric panel 18 Contactor 19 Thermaloverloadprotection 20 Motor 21 Lockingdevice flange 22 Solenoidv...

Страница 4: ...Flange burner tube Measure B Burner head Standard 290 260 Burner head Long design 390 360 595 290 155 158 B 610 321 400 405 171 215 78 00 02 BURNER HEAD Brake plate 130 The net calorific value of 11 8...

Страница 5: ...171 215 79 00 02 BURNER HEAD Brake plate 120 BURNER HEAD Brake plate 110 10 0 13 0 10 0 13 0 3 5 4 0 2 0 3 0 7 0 9 0 3 5 4 0 2 0 3 0 7 0 9 0...

Страница 6: ...TECHNICAL DATA DIMENSIONS OF FLANGE 171 225 37 00 01 14 226 254 295 160...

Страница 7: ...is obtained If larger nozzles are usedthepreadjustmentofboththeair volumeandthenozzleassemblymust be increased Awhistlingsoundmaybeheardwhich can be eliminated or reduced as fol lows Increase the noz...

Страница 8: ...stage Set the operating switch S2 on low capacity I Loosenthescrew A and turn the damper to the position wan ted Tighten the screw A again Second stage Set the operating switch S2 on high capacity II...

Страница 9: ...il supply 171 305 65 01 01 SERVICE OF BURNER HEAD alt A SERVICE OF BURNER HEAD alt B NOTE For maintenance of the brake plate nozzles electrodes etc when using a long design of the burner tube you have...

Страница 10: ...itch high low capacity S3 Controlthermostat S4 Temperaturelimiter S5 Micro switch for hinged door S6 Control thermostat high low capacity S7 Main switch S12 External reset button S20 Main switch T1 Ig...

Страница 11: ...n thermostat The burner motor starts an ignition spark is formed the prepurge goes on till the prepurge period expires and the solenoid valve 1 opens 2 2 Solenoidvalve1opens Oil mist is formed and ign...

Страница 12: ...pingapipesystemusuallycomprises 4elbows anon returnvalve acut off valve and an external oil filter Thesumoftheseindividualresistances is so insignificant that they can be disregarded Thetablesdonotinc...

Страница 13: ...h return port R closed MOUNTING DISMOUNTING BY PASS PLUG In a 2 pipe system excess oil is led back direct to the oil tank In a 1 pipe system the by pass plug must be removedsothatthereisafreepassage b...

Страница 14: ...255 219 22 43 266 229 23 34 277 238 24 23 287 247 25 07 297 256 25 91 307 264 26 70 317 272 6 00 22 34 265 228 23 42 278 239 24 47 290 250 25 46 302 260 26 43 313 270 27 49 326 280 28 27 335 288 29 13...

Страница 15: ...not reset Appliance overheat device has operated Control relay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue dr...

Страница 16: ...B20 B30 B40 B45 02119815004 B50 B60 B70 B80 040588622001 B55 040588622002 B65 Enertech AB declares under sole responsibility that the above mentioned product is in conformity with the following stand...

Страница 17: ......

Страница 18: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 19: ......

Страница 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...