background image

GENERAL INSTRUCTIONS

General Rules

The installation of an oil burner should 
be carried out in accordance with local 
regulations. The installer of the burner 
must therefore be aware of all regula-
tions relating to oil and combustion.
Only oil suitable for the burner should 
be used and then in combination with 

a suitable oil ilter before the oil pump 

of the burner.
If the burner is replacing an existing 

burner make sure that the oil ilter is 

replaced or cleaned. The installation 
must only be undertaken by experienced 
personnel. Care should be taken by 
the installer to ensure that no electrical 
cables or fuel/gas pipes are trapped or 
damaged during installation or service/
maintenance.

Installation instructions

General installation instructions 

 

accompany the burner and should be 
left in a prominent place adjacent to 
the burner.

Adjustment of burner

The burner is from the factory pre-set 
to an average value that must then 
be adjusted to the boiler in question.
All burner adjustments must be made 
in accordance with boiler manufacturers 
instructions.These must include the 

checking  of  lue  gas  temperatures, 

average water temperature and CO

2

 

or O

2

 concentration.

To adjust the combustion device, 
start by increasing the air volume 
and the nozzle assembly somewhat. 
When the burner starts it is  burning 
with excess air and smoke number 0.  
Reduce the nozzle assembly adjust-
ment until soot occurs, and then 
increase the adjustment to make 
the soot disappear again. Then the 
volume of air is reduced until soot 
occurs and increased again to reach 
a combustion free of soot.
By this procedure an optimum adjust-
ment is obtained. If larger nozzles are 
used the preadjustment of both the 
air volume and the nozzle assembly 
must be increased.
A whistling sound may be heard which 
can be eliminated or reduced as fol-
lows: Increase the nozzle
assembly adjustment somewhat. The 
CO

2

-content and consequently the air 

volume will then be reduced.

Condensation in chimney

A modern burner works with less ex-
cess air and often also with smaller 

nozzles than older models. 

This increases the eficiency but also 

the risk of condensation in the chim-
ney. The risk increases if the area 

of the chimney lue is too large. The 

temperature of the lue gases should 

exceed 60°C measured 0,5 metres 
from the chimney top.
Measures to raise the temperature:
Insulate the chimney in cold attics
Install a tube in the chimney
Install a draught regulator (dilutes the 

lue gases during operation and dries 

them up during standstill)
Increase the oil quantity

Raise the lue gas temperature by re

-

moving turbulators, if any, in the boiler.

Pump adjustment

See separate description.

Air adjustment

See page "Air adjustment with 
damper motor".

Maintenance

The boiler/burner should be examined 
regularly for any signs of malfunction 
or oil leakage. 

Oil supply

The oil line should be dimensioned 
in accordance with the pump manu-
facturer´s instruction. In the suction 

line  to  the  burner  a  ilter  should  be 

mounted to prevent any particles in 
the oil from reaching the burner. If the 
installation consists of several burners 
each one should have its own suc-
tion line from the tank or a circulation 
system should be used. 
The temperature in the oil line should 
be kept as constant as possible. 
Avoid exposing the line to excessive 
cold which may cause blockages of 

parafin deposits. 

The oil pipe and electric cable should 

be  itted  so  that  the  burner  can  be 

placed on the loor for inspection of 

the combustion device.

Adjustment of nozzle assembly

Loosen the locking screw B and adjust 
the nozzle assembly to the desired 
position. Lock the screw B again.

171 305 11  10-01

B

Содержание Bentone B 40 A2.2

Страница 1: ...Providing sustainable energy solutions worldwide 178 019 54 Installation and maintenance instruction B 40 A2 2 ...

Страница 2: ......

Страница 3: ...set button 9 Electric panel 10 Cover inspection glass 11 Indicating lamp 12 Change over switch 13 Fan wheel 14 Motor 15 Nozzle assembly adjustment 16 Blast tube 17 Damper motor 18 Connecting pipe Stage 2 Burner with two nozzles 19 Air damper 20 Air intake 21 Connecting pipe Stage 1 22 Solenoid valve 23 Pump Components 171 205 06 07 01 ...

Страница 4: ...mended nozzle Because of different boiler types ex isting on the market with varying combustion chamber designs it is not possible to state a deinite spray angle or spray pattern Note that the spray angle and the spray pattern change with the pump pressure Type designation B40A2 171 225 60 10 01 The net caloriic value of 11 86 kWh kg for light oil has been used 207 435 B 420 ø130 ø114 260 310 360 ...

Страница 5: ...mbly must be increased Awhistlingsoundmaybeheardwhich can be eliminated or reduced as fol lows Increase the nozzle assemblyadjustmentsomewhat The CO2 contentandconsequentlytheair volume will then be reduced Condensation in chimney A modern burner works with less ex cess air and often also with smaller nozzles than older models This increases the eficiency but also the risk of condensation in the c...

Страница 6: ...Seeig Low capacity Adjust the operating switch to high capacity II Reduce the air volume Turn orange cam towards 0 Increase the air volume Turn orange cam towards 90 Adjust the operating switch back to low capacity and check Full capacity Adjust the operating switch to low capacity I Reduce the air volume Turn red cam towards 0 Increase the air volume Turn red cam towards 90 If the red cam is move...

Страница 7: ...the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A and nut B Service of burner head 171 305 53 10 01 1 Loosen or swing out the burner from the boiler 2 Loosen 2 ixing screws and with draw the blast tube ...

Страница 8: ...TRIC EQUIPMENT Oil burner control LOA21 LOA24 Wiring diagram If the boiler is not equipped with wired contacts connect the enclosed contacts to terminals X4 and X6 in accordance with wiring diagram 1 2 1N 50 60Hz 230 V 1 3 ...

Страница 9: ...2 Operating switch high low capacity S3 Control thermostat S4 Temperature limiter S5 Micro switch for hinged door S6 Control thermostat high low S7 Main switch T1 Ignition transformer X1 Connection terminal board X2 Earth terminal X3 Plug in contact burner X4 Plug in contact boiler X5 Plug in contact high low capacity burner X6 Plug in contact high low capacity boiler Y1 Solenoid valve 1 Y2 Soleno...

Страница 10: ...erating position and can now change between full load and low load 4 5 Operating position If the burner operation is interrupted by means of the main switch or the thermostat a new start takes place when the conditions in accordance with point 1 are fulilled The oil burner control cuts out A red lamp in the control is lit Press the reset button and the burner re starts Post ignition 2 If a post ig...

Страница 11: ...h in metres at a nozzle capacity of 9 5 Gph Max permissible pres sure at the suction and pressure side is 2 0 bar Components 1 Nozzle outlet G 1 8 Stage 2 2 Pressure gauge port G 1 8 3 Nozzle outlet G 1 8 Stage 1 4 Pressure gauge port G 1 8 5 Vacuum gauge port G 1 8 6 Return line G 1 4 and internal by pass plug 7 Suction line G 1 4 8 Return plug 9 Pressure adjustment 10 Solenoid valve 1 11 Solenoi...

Страница 12: ...ic it is assured by a bleed lat on the piston In one pipe operation a high pressure connection must be loosened until the air is evacuated from the system Cut Off The solenoid valves of the A2L pump are of the normally closed type and are situated in the nozzle lines This design ensures extremely fast res ponse and the switching can be sel ected according to the burner opera ting sequence and is i...

Страница 13: ... 93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14 89 176 152 15 62 185 159 4 50 14 97 177 153 15 88 188 162 16 75 198 171 17 57 208 179 5 00 16 64 197 170 17 65 209 180 18 62 221 190 19 52 231 199 5 50 18 30 217 187 19 42 230 198 20 48 243 209 21 47...

Страница 14: ...11 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 97 201 173 17 62 209 180 18 23 216 186 4 50 18 35 217 187 19 10 226 195 19 82 235 202 20 51 243 209 5 00 20 39 242 208 21 22 251 216 22 03 261 225 22 79 270 232 5 50 22 43 266 229 23 34 277 238 24 23 ...

Страница 15: ...of magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocell defective No oil being delivered Excessive lue draught is preventing lame establishment No spark Check or replace fuse if necessary Check reason for failure Adjust thermostat Reset overheat device ...

Страница 16: ...ont conformes aux normes et aux documents normatifs suivants et satisfont aux critères applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suivantes 2004 108 EC Elektromagnetisk kompatibilitet Electromagnetic compatibility EC Richtlinie Compatibilité électromagnétique 2006 95 EC Lågspänningsdirektivet Low voltage directive Niederspannungs Ric...

Страница 17: ... the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If the burner starts but does not ignite Make an attempt to start the burner Never make close repeated start attempts Don t restart the burner until the boiler is free from oil gases If the burner stil...

Страница 18: ......

Страница 19: ......

Страница 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...

Отзывы: