OutBack Power
| Commissioning Document
©2019 OutBack | an EnerSys company
FA
-KF-10/
11
/2019
Page 8 of 12
(Optional) Advanced Generator Start
For a stack, only the master controls the generator through advanced generator start (AGS).
Connect the generator start circuit to the auxiliary dry contacts (7 and 15) or the 12V contacts
(8 and 16) on the master auxiliary terminal. Enable and program AGS on the master SkyBox only.
(Optional) External CT
If using external current transducers (CT), connect them to the master unit. Enable this function on
the master SkyBox only.
(Home screen
SkyBox icon
Configure
Edit
arrow down once)
Enabling this function causes the master SkyBox display to show the total grid demand seen
at the external CT location. This measurement is used to calculate the
Total Combined Load
value that is displayed on the master SkyBox
LOAD
tile. Under the load tile, protected and
unprotected load values are shown (Figure 10).
Figure 9 – XCT setup menu
Figure 10 – Protected and unprotected loads