Installation and Operation
6
900-00264-01-001 Rev A
Materials Required
Tools (use insulated tools only)
o Digital
voltmeter
o Socket wrench
o Torque wrench calibrated in inch-pounds
o Box end wrench
o Battery lifting equipment (handles) and fork lift to lift pallets of batteries
o Rubber
gloves
o Full
face
shield
o Plastic
apron
o Portable
eyewash
o Spill
kit
o Fire extinguisher (class C)
Accessories
o Interconnect bar (included)
o Terminal cover (included)
o Hardware
(included)
o Interconnect cables as needed
CAUTION: Fire Hazard
Install properly sized battery cabling and interconnect cables. The cable ampacity
must meet the needs of the system, including temperature, deratings, and any other
code concerns.
Storage and Environment Requirements
Temperatures
o Optimal operating temperature is 68° to 86° F (20° to 30°C); maximum temperature range is
–40° to 149°F (–40° to 65°C).
o Do not allow a discharged battery to freeze, as this will damage them and could result in leakage.
o Do not expose batteries to temperature variations of more than 5°F (3°C). This leads to voltage
imbalance between multiple batteries (or between battery cells if there is a temperature differential).
o Batteries should be stored in a cool, dry location.
Содержание OutBack POWER NorthStar NSB BLUE+ Series
Страница 1: ...NorthStar NSB BLUE Owner s Manual...
Страница 14: ...Installation and Operation 14 900 00264 01 001 Rev A NOTES...
Страница 24: ...Maintenance 24 900 00264 01 001 Rev A NOTES...
Страница 27: ...EnergyCell Batteries 900 00264 01 001 Rev A 27 This page intentionally left blank...
Страница 28: ...Masters of the Off Grid First Choice for the New Grid 17825 59th Avenue N E Suite B Arlington WA 98223 USA...