background image

Radian Series  

900-0128-01-00 Rev C

Figure 6 

Power Module Nuts and Handholds 

9.

Using the two handholds provided on the Power Module, lift up at least 1 inch and then outwards to remove the 
Power Module. 

10. Insert the replacement Power Module by reversing steps 1 through 9.  Tighten the nuts in step 8 to a torque value 

of 60 to 68 in-lbs.  Refer to Table 1 for model specific locations of the transformer wires, fan wires and ribbon cables.

11. Proceed to the 

Replacement of the Front Cover

 section.

Replacement of the Front Cover 

Tools 

Phillips screwdriver 

Procedure 

To replace the front cover: 

1.

Prior to replacement of the cover ensure no tools or loose hardware has been left inside the chassis.  Also ensure 
that all electrical connections have been made.  These include the AC input and output terminations, ground 

termination, Remote cable, Auxiliary wires, Battery Temp cable, two ribbon cables (both ends), two fan cables, and 

the four or six connections from the Power Module to the PCBA Module. 

NOTE

:  For Radian models that have only one Power Module there is only one ribbon cable, one fan, and either two 

or three connections from the Power Module to the PCBA Module.  In this case it is necessary to use the “Left” 

connections 

2.

Use a Phillips screwdriver to insert the 22 screws that attach the cover to the chassis.  Tighten screws to “finger 
tight,” as excessive torque may warp the cover.  Refer to Figure 2. 

Power Up 

After replacement of internal items it is necessary to power up the Radian inverter and other related 

electronics to check that the repair has been successful.  If only a Power Module has been replaced, please 

proceed through the steps below, ignoring those pertaining to firmware updates and configuration files.  If 
the PCBA Module was replaced, it may need to be programmed in order for proper system operation.  

Additionally, the firmware revision number will need to be the same as the firmware of other Radian 

inverters in the system if they are present.   

IMPORTANT:  MATE3 Upgrade 

When replacing the PCBA Module, make certain to upgrade the MATE3 firmware to the 
latest revision.  If it is not upgraded, the MATE3 may not recognize any new inverter 
functions.  This will make them inaccessible to the user.  See the OutBack website, 

www.outbackpower.com 

or AOE website www.alpha-outback-energy.com

 

, for the 

latest firmware revisions. 

Remove these 2 nuts 

Handholds 

Handholds

Содержание OutBack Power ALPHA OUTBACK ENERGY Radian Series

Страница 1: ...ng the PCBA Module performing these tasks will be helpful to return the inverter to its previous operational parameters See the MATE3 System Display and Controller Operator s Manual for details IMPORTANT MATE3 Upgrade When replacing the PCBA Module make certain to upgrade the MATE3 firmware to the latest revision If it is not upgraded the MATE3 may not recognize any new inverter functions This wil...

Страница 2: ... OUT HOT L1 GRID IN HOT L2 AC OUT HOT L2 GEN IN HOT L1 GRID IN HOT L1 GEN IN HOT L2 Removal of Cover Tools Phillips screwdriver Procedure To remove the front cover 1 Use a Phillips screwdriver to remove the screws that attach the cover to the chassis 2 Pull cover directly out from the chassis 3 Set aside the cover and the cover screws Figure 2 Radian Inverter With Cover and Without Cover DC Termin...

Страница 3: ...secure the transformer wires Note the locations of the wires for later reference If possible take a photograph of the wire placement prior to disconnection For some Radian models the type of terminal block shows markings on the terminal blocks L1 Black L2 Red N Neutral and below them on the circuit board RIGHT XFMR LEFT XFMR and NEUTRALS that identify the correct connections For other Radian model...

Страница 4: ... and 8 to a torque value of 60 to 68 in lb Refer to Tabke 1 for model specific locations of transformer wires fan wires and ribbon cables 11 Proceed to the Replacement of the Front Cover section on page 6 Table 1 Radian Model Connection Locations Model Power Module Position Black Wire Terminal White Wire Terminal Red Wire Terminal Fan Cable Terminal Ribbon Cable GS8048 Left L1 LEFT XFMR N NEUTRALS...

Страница 5: ...the wire Repeat for the remaining wire s connected to the module that is to be replaced Pull the wires free from the terminals See image A in Figure 3 If the terminal block does not have locking tabs insert the screwdriver horizontally into the terminal block slot for each wire Lever the screwdriver outward from the back of the housing to the front This releases the tension on the wire Repeat for ...

Страница 6: ... and either two or three connections from the Power Module to the PCBA Module In this case it is necessary to use the Left connections 2 Use a Phillips screwdriver to insert the 22 screws that attach the cover to the chassis Tighten screws to finger tight as excessive torque may warp the cover Refer to Figure 2 Power Up After replacement of internal items it is necessary to power up the Radian inv...

Страница 7: ... inverters in a system must have the same firmware revision number After replacing a PCBA module in a system with multiple Radian inverters the replacement should contain the latest firmware available This revision may not match other inverters in the system but contains equivalent or improved functionality and features Make certain the latest revision is installed It can be found on the OutBack w...

Страница 8: ...FORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK Notice of Copyright Radian Series Inverter Charger Service Instructions March 2014 by OutBack Power Technologi...