background image

Radian Series  

900-0128-01-00 Rev C

Figure 1 

DC Terminals 

Verify no AC voltage is present between the following terminals and ground.  These connections may be located in 

an electrical distribution box near the inverter.  Some systems have no “L2” terminals. 

~

 

AC OUT HOT L1 

~

 

GRID IN HOT L2

~

 

AC OUT HOT L2 

~

 

GEN IN HOT L1

~

 

GRID IN HOT L1 

~

 

GEN IN HOT L2

Removal of Cover 

Tools 

Phillips screwdriver 

Procedure 

To remove the front cover: 

1.

Use a Phillips screwdriver to remove the screws that attach the cover to the chassis.

2.

Pull cover directly out from the chassis.

3.

Set aside the cover and the cover screws.

Figure 2 

Radian Inverter With Cover and Without Cover  

DC – Terminal 

DC + Terminal 

DC + Terminal

DC – Terminal 

Remove screws (x22) 

Содержание OutBack Power ALPHA OUTBACK ENERGY Radian Series

Страница 1: ...ng the PCBA Module performing these tasks will be helpful to return the inverter to its previous operational parameters See the MATE3 System Display and Controller Operator s Manual for details IMPORTANT MATE3 Upgrade When replacing the PCBA Module make certain to upgrade the MATE3 firmware to the latest revision If it is not upgraded the MATE3 may not recognize any new inverter functions This wil...

Страница 2: ... OUT HOT L1 GRID IN HOT L2 AC OUT HOT L2 GEN IN HOT L1 GRID IN HOT L1 GEN IN HOT L2 Removal of Cover Tools Phillips screwdriver Procedure To remove the front cover 1 Use a Phillips screwdriver to remove the screws that attach the cover to the chassis 2 Pull cover directly out from the chassis 3 Set aside the cover and the cover screws Figure 2 Radian Inverter With Cover and Without Cover DC Termin...

Страница 3: ...secure the transformer wires Note the locations of the wires for later reference If possible take a photograph of the wire placement prior to disconnection For some Radian models the type of terminal block shows markings on the terminal blocks L1 Black L2 Red N Neutral and below them on the circuit board RIGHT XFMR LEFT XFMR and NEUTRALS that identify the correct connections For other Radian model...

Страница 4: ... and 8 to a torque value of 60 to 68 in lb Refer to Tabke 1 for model specific locations of transformer wires fan wires and ribbon cables 11 Proceed to the Replacement of the Front Cover section on page 6 Table 1 Radian Model Connection Locations Model Power Module Position Black Wire Terminal White Wire Terminal Red Wire Terminal Fan Cable Terminal Ribbon Cable GS8048 Left L1 LEFT XFMR N NEUTRALS...

Страница 5: ...the wire Repeat for the remaining wire s connected to the module that is to be replaced Pull the wires free from the terminals See image A in Figure 3 If the terminal block does not have locking tabs insert the screwdriver horizontally into the terminal block slot for each wire Lever the screwdriver outward from the back of the housing to the front This releases the tension on the wire Repeat for ...

Страница 6: ... and either two or three connections from the Power Module to the PCBA Module In this case it is necessary to use the Left connections 2 Use a Phillips screwdriver to insert the 22 screws that attach the cover to the chassis Tighten screws to finger tight as excessive torque may warp the cover Refer to Figure 2 Power Up After replacement of internal items it is necessary to power up the Radian inv...

Страница 7: ... inverters in a system must have the same firmware revision number After replacing a PCBA module in a system with multiple Radian inverters the replacement should contain the latest firmware available This revision may not match other inverters in the system but contains equivalent or improved functionality and features Make certain the latest revision is installed It can be found on the OutBack w...

Страница 8: ...FORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK Notice of Copyright Radian Series Inverter Charger Service Instructions March 2014 by OutBack Power Technologi...