7

C048-702-30 R02, Rev. B (03/2021)

4.2  

4.2  Installation Procedure

Installation Procedure

THIS PRODUCT MUST BE INSTALLED WITHIN A RESTRICTED ACCESS LOCATION WHERE ACCESS IS 

THROUGH THE USE OF A TOOL, LOCK AND KEY, OR OTHER MEANS OF SECURITY, AND IS CONTROLLED 

BY THE AUTHORITY RESPONSIBLE FOR THE LOCATION� THIS PRODUCT MUST BE INSTALLED AND 

MAINTAINED ONLY BY QUALIFIED TECHNICIANS�

NOTICE:

WARNING! ELECTRICAL HAZARD

VRLA BATTERY STACKS CAN PROVIDE THOUSANDS OF AMPERES OF DISCHARGE CURRENT INTO 

A SHORT CIRCUIT, IN ADDITION, PARALLELED BATTERY STACKS AND LARGE RECTIFIER SYSTEMS 

CAN ALSO DISCHARGE EXTREMELY HIGH CURRENTS INTO A SHORT CIRCUIT FAULT� THERE IS 

AN EXTREME SAFETY HAZARD WHEN WORKING ON LARGE SYSTEMS WITH THIS DISCHARGE 

AMPACITY POTENTIAL� EYE PROTECTION, SAFETY GLOVES AND PROTECTIVE SHIELDS ARE 

REQUIRED ENTIRELY DURING THE TRD INSTALLATION PROCESS�

Step 1. 

Unpack and inspect contents of TRD kit. See "3.1 Package Contents" on page 6 for more information. Confirm 

all parts are present and no shipping damage has occurred�

Step 2. 

Installation into the DCX unit technically can be performed with the battery disconnect circuit breaker on and 

connected to the rectifier and load system in extreme cases but is not recommended for safety reasons and due 

to the fact that battery bus bar connections must be loosened as part of the temperature sensor installation 

process. It is recommended that the battery disconnect circuit breaker be turned off for the installation process.

Step 3. 

Locate the DCX unit to be retrofitted with the TRD kit. Turn off the DCX circuit breaker and tape in the off position 

as a reminder during the work process and as a notification to co-workers that may be present. Ensure that eye 

protection, safety gloves, long sleeve shirts are used as a precaution�

Step 4. 

Open the flip-up DCX unit lid/door and confirm that it latches in the secure upright position.

Step 5. 

Install the TRD circuit board and control assembly from the left of the DCX unit and move toward the right to plug 

into the expansion connector on the existing circuit board assembly inside of the DCX unit� Ensure that there is a 

secure connection with full alignment and seating of the connectors� Align the mounting holes of the TRD board 

assembly with the existing threaded metal stand-offs inside of the DCX unit. Install the screws provided in the kit 

to secure the TRD board module assembly to the DCX metal housing�

Step 6. 

Locate the temperature sensor kit which consists of two remote terminal temperature sensors and cable 

assemblies� Note that one cable may be shorter than the other� One temperature sensor and cable is intended to 

mount on a battery terminal near the top of the battery stack which requires a shorter cable, while the other 

sensor is intended to be installed on the lower section of the battery stack, requiring the longer cable to route to 

this location�

Step 7. 

Installation of the temperature sensor modules requires that the bolt connecting the copper bus strap that will be 

used to mount the sensor be removed and replaced with a longer bolt to mount the TRD sensor module� This 

requires access to the battery terminals and is a safety hazard area� Ensure that insulated tools, safety gloves, 

and eye protection are used�

Step 8. 

To install the temperature sensor modules, two mounting locations must be confirmed: one at the top of the 

battery stack to monitor the upper section of the stack and one near the lower third of the stack to monitor lower 

stack temperature�  

 

These two temperature sensing points are compared to an ambient temperature sensor in the TRD unit to 

determine the temperature rise of the battery sensors compared to ambient and compared to each other� The 

temperature sensor module has a copper lug with a clearance hole for a 1⁄4-20 bolt which is the typical size bolt 

used in the strapping kit from the battery manufacturer. Confirm that the DCX circuit breaker is in the OFF 

position, then remove the appropriate clear cover from the battery stack that is covering the bolt location desired 

for installation� Ensure that insulated tools, safety gloves, and eye protection are used� Carefully loosen and 

remove the bolt while being extremely careful to not contact adjacent battery terminal posts or strap locations� 

Remove this bolt and washers and nut and set aside�

Содержание Alpha TRD

Страница 1: ...TRD VRLA Battery Thermal Runaway Detection System for DCX Series Battery Disconnect Systems Technical Manual Effective March 2021...

Страница 2: ...fumes safety information to PREVENT INJURY OR DEATH to the technician or user WARNING FUMES HAZARD FIRE HAZARD WARNING provides flammability safety information to PREVENT INJURY OR DEATH to the techn...

Страница 3: ...his powering system please contact Alpha Technologies Services Inc or your nearest Alpha representative Alpha shall not be held liable for any damage or injury involving its enclosures power supplies...

Страница 4: ...lation 6 4 1 Installation Preparation 6 4 1 1 Elevated Operating Ambient Temperature 6 4 1 2 Reduced Air Flow 6 4 1 3 Mechanical Loading 6 4 1 4 Circuit Overloading 6 4 1 5 Reliable Earthing 6 4 1 6 D...

Страница 5: ...ker and disconnect the battery string from the load and rectifier system Manual disconnect is always available via simply turning off the circuit breaker handle The TRD option Thermal Runaway Detector...

Страница 6: ...ure that all of the following conditions are met before proceeding 4 1 1 4 1 1 Elevated Operating Ambient Temperature Elevated Operating Ambient Temperature If you install the product in a closed or m...

Страница 7: ...circuit board assembly inside of the DCX unit Ensure that there is a secure connection with full alignment and seating of the connectors Align the mounting holes of the TRD board assembly with the ex...

Страница 8: ...bottom of the stack and repeat the installation procedure from Step 9 for this sensor Confirm all connections are tight Step 11 Locate temperature sensor cables and confirm that they are different len...

Страница 9: ...NC normally closed C common Max 1 ampere 30VDC y Actuates first if a thermal fault is initially detected Can be wired to a remote strobe lamp horn etc to notify alert condition locally Can be wired to...

Страница 10: ...connect Figure 7 Internal TRD detect and remote disconnect control Option B Internal TRD detect and remote disconnect control This option requires use of a remote controller device of some kind such a...

Страница 11: ...tions Input Voltage 48V DC supplied by DCX unit term board Width 7 25 in Height 5 5 in Operating Temperature 0 to 50 C Elevation 500m to 2800m 7 0 7 0 Ordering Information Ordering Information Table 5...

Страница 12: ...Technical Support 1 800 863 3364 For more information visit our website at www alpha com 2021 Alpha Technologies Services Inc All Rights Reserved Trademarks and logos are the property of Alpha Techno...

Отзывы: