background image

 

For more information visit www.alpha.com  

Page 3 of 6 

 
 

Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 

0470453-TAB Rev A (04/2020) 

Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice.

 

 

F-MKT-04 Rev 1.4 

Configuration 2:

 Recommended Grounding of SE41 RPN with Remote AC Service Disconnect located 

within four feet of the SE41 cabinet 
 
Objective: 
Install a 

continuous

 length of #2AWG tinned solid copper conductor originating at the ACEG bus in the remote 

service disconnect enclosure and have it terminated at the Enclosure Master Ground Bar (MGB). 

Steps: 

1.

 

Connect the #2AWG tinned solid copper conductor to the ACEG bus in the remote service 
disconnect enclosure and then to the ground rod nearest to the Enclosure MGB. 

2.

 

Terminate  this  Grounding  Electrode  Conductor  (GEC)  to  the  Enclosure  MGB  using  an 
appropriate two-hole compression lug (

refer to Figure 2).

 

 

Note:

 

Avoid tight radius bends.

 

It is recommended that all buried grounding connectors are 12” 

below  finished  grade  line  or  below  the  frost  line.

 

For  below  grade  connections,  crimp  or 

mechanical connectors may be used instead of an exothermic weld provided they are listed 
for direct burial applications. 

 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 2 

 SE41 RPN with remote disconnect (<4') grounding diagram

 

Отзывы: