Configuration 1: 

Recommended grounding of SE41 RPN with combination meter and load center 

 

1.

 

Install  a  #2AWG  tinned  solid  copper  site  ground  wire  (grounding  electrode  conductor) 
originating  at  the  closest  driven  ground  electrode  and  connect  it  to  the  Load  Center  AC 
Equipment Ground (ACEG) bus (

refer to Figure 1

).  

 

Note: 

It is recommended that all buried grounding connectors are 12” below finished grade 

line or below the frost line.

 

For below grade connections, crimp or mechanical connectors may 

be used instead of an exothermic weld provided they are listed for direct burial applications.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2.

 

Route  a  length  of  #2AWG  tinned  solid  copper  conductor  from  a  junction  point  on  the 
grounding electrode conductor (GEC)and connect to the Enclosure Master Ground Bar (MGB) 
using an appropriate compression two-hole lug (

Refer to Figure 1)

.  

Note:

 

Avoid tight radius bends and route the conductor such that it intersects with the GEC at 

a downward orientation as illustrated in Figure 1. 

 

3.

 

Connect the other end of the conductor to the GEC via an irreversible compression 
connector or exothermic weld.

 

 

Figure 1 

 SE41 RPN combo meter & load center grounding diagram

 