55
APPENDIX F – ADjUSTING GAS INPUT RATE
Natural Gas Boilers:
1.
Turn off gas supply to all appliances other
than gas-fired boiler.
2.
Note the rated manifold gas pressure listed
on the boiler’s rating label.
3.
Connect Manometer to manifold pressure
tapping on Gas Valve (Figure F-1).
4.
Light main burners by adjusting thermostat
to highest setting.
5.
If required, adjust gas manifold pressure to
the rated setting by turning the gas valves
adjustment screw clockwise to decrease
manifold pressure or counterclockwise to
increase manifold pressure (Figure F-2).
Several turns may be required.
Do not force the adjustment screw.
6.
On models using more than one gas valve,
turn “off” the gas valve not having pilot
control and first adjust the gas valve with
pilot control. Then, turn “on” both gas valves
and adjust the gas valve without pilot control.
7.
Clock gas meter for at least two (2)
revolutions of the dial typically labeled ½ or
1 cubic foot per revolution on a residential
gas meter.
8.
Determine gas flow rate in Cubic Feet
per Hour based on elapsed time for two
revolutions. (Example: 70 Seconds for (2)
Revolutions = 102.8 Cu. Ft.
9.
When the clocked time falls between two
table values (Table F-1), add the table
values shown above and below your clocked
reading and divide by 2 (Example: 68
Seconds for (2) Revolutions = (110.7+102.8)
/2 = 106.7 Cu. Ft./Hr.).
10.
Obtain gas-heating value (Btu per cubic
foot) from gas supplier or use nominal
value of 1000 Btu per cubic foot.
11.
Multiply gas flow rate by gas heating value.
(Example: 70 Seconds for (2) Revolutions
= 120.8 Cu. Ft./Hr. X 1027 Btu/Cu. Ft. =
124,061 Btu/ Hr.
12.
Compare measured input rate to input rate
stated on rating label.
DO NOT EXCEED
the boiler’s rated gas
input.
13.
If input is too high, reduce input rate by
decreasing manifold pressure. Do not
reduce more than 0.3” w.c. Instead, contact
U.S. Boiler Company for an orifice
replacement kit.
14.
If input is below 98% of Rating Label input,
increase manifold gas pressure no more
than 0.3 inches w.c. If measured rate is still
F-1
F-2
Содержание ESC
Страница 6: ... Figure S 1 Minimum Clearances to Combustibles SPECIFICATIONS continued ...
Страница 30: ...30 Internal Wiring Figure IW 1 Wiring Diagram ...
Страница 31: ...31 Internal Wiring continued Figure IW 2 Wiring Diagram ...
Страница 37: ...37 APPENDIX B1 INTENTIONALLY OMITTED ...
Страница 50: ...50 Figure D 0 Piping Schematic Symbols APPENDIX D System Piping continued ...
Страница 62: ...62 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 63: ...63 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 64: ...64 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 717 397 4701 www usboiler burnham com ...