background image

www.hi-velocity.com

Module RCM-I

RCM-I Installation

Outdoor Unit Installation

Locate the outdoor unit in a suitable location, as close as 

possible to the fan coil. Maintain the clearances recommended 

in the HVS Variable Speed Heat Pump manual to ensure proper 

airflow. The outdoor unit must be installed level, in a properly 

supported location. If proper refrigerant piping techniques  are 

used, a liquid line bi-directional filter/drier is not needed.  More 

information can be found in module HVS - Variable Speed Heat 

Pump Manual.

Evacuating

The system must be brazed under a nitrogen purge to 

prevent oxidation of the pipe during the brazing process.  After 

the piping is installed and all components have been brazed 

together, a vacuum pump must be used to properly evacuate 

the system from both of the access ports to 1500 microns, to 

ensure system is free of contaminants.  Add refrigerant to the 

system to bring the pressure above zero psig. After allowing 

the refrigerant to absorb moisture, repeat the above procedure. 

Evacuate the system to 500 microns on the second evacuation, 

and ensure that the system holds at the vacuum pressure. If not, 

check for leaks and evacuate again. If the vacuum holds, add 

refrigerant to raise the pressure to 2 psig. At this point open 

service valves on pre-charged condensing units.

The use of an electronic leak detector is recommended, as it is 

more sensitive to small leaks under the low pressures.

Once the system has been determined clean and ready for 

charging, refrigerant can be added. The service valves on the 

condenser must be open at this time.  By referring to page 5 in 

the HVS Heat Pump Manual, if additional refrigerant is needed, 

weigh in the recommended amount.   Truly, the only way to tell 

if the system is properly charged is by pulling out all refrigerant, 

then weighing it back in based on the factory charge listed on 

the rating plate, plus any additional refrigerant needed based 

on page 5 of Module HVS - Variable Speed Heat Pump Manual.

Charging

Wiring – Outdoor Unit

Make all connections to the outdoor unit with rain tight 

conduit  and  fittings.  Most  building  codes  require  a  rain  tight 

disconnect switch at the outdoor unit as well (always check 

local codes). Run the proper size copper wires to the unit, and 

connect as per the manufacturer’s recommendations.

The RCM-I coil can operate at a level that is different from most 

other conventional system coils. This coil is supplied refrigerant 

by a variable speed condenser/compressor, so refrigerant 

pressures and temperature can vary as well.   Temperature 

and pressure reading aren’t as important for a refrigeration 

technician to know in a variable speed heat pump condensing 

unit. 

Important:

  

Failure to follow the proper 

evacuating and charging procedures may 

void warranty.

Carry-over Screen

All RCM-I refrigerant cooling modules come supplied with 

a  nylon  mesh  carry-over  screen  and  six  stand-off  plugs.    The 

Hi-Velocity units have a very high humidity removal rate, it is 

possible for the airflow across the coil to grab moisture off the 

fins and carry it into the unit.  With the carry-over screen in place 

it reduces the chance of moisture being carried into the unit.

Ensure that the nylon mesh is placed on the exiting air side of 

the cooling module (Fig. 4)

Installation Instructions

The Carry Over Screen is placed on fan coil side of the cooling 

module (Fig. 04).

Fig. 04 - Screen on the fan coil side

On the fan coil side of the cooling module, attach three plastic 

stand-offs down each side of the cooling coil (Fig. 05).

Fig. 05 - Attach stand-off plugs

Place the nylon wire mesh over the stand-offs, ensuring the 

screen touches the drain pan. Then snap the screen over the 

plastic stand-offs (Fig. 06).

Fig. 06 - Attach screen to coil

Module RCM-I - RCM-I Coil Installation (4/8)

Содержание Hi-Velocity RCM-I Series

Страница 1: ...nt Module Installation Manual Small Duct High Velocity Heating Cooling and Home Comfort Systems RCM I 70 2 5 3 Tons RCM I 100 3 5 5 Tons Includes Service Access Ports L Mounting Brackets Double Sided Mounting Tape Carry Over Screen For use with HVS 36 HVS 60 Variable Speed Heat Pumps ...

Страница 2: ... is for use with HVS 36 and HVS 60 Inverter Heat Pump Condensing Units It does not come with thermal expansion valve as there are internal EXVs inside the Heat Pump When installing the RCM I Modules DO NOT INSTALL WITH TXVs The module will come with access ports that will need to be installed to read refrigerant pressures temperatures at the Evaporator RCM I Fig 01 shows approximate installation l...

Страница 3: ...pipe every 5 feet or whatever local code states Run the pipes in the most direct route possible taking into account structural integrity building details and local building codes Minimum refrigerant pipe length is 16ft 6m If going less than 16 ft coil the additional copper pipe up in horizontal loops to ensure proper oil return If the evaporator is located above the condenser slope any horizontal ...

Страница 4: ... out all refrigerant then weighing it back in based on the factory charge listed on the rating plate plus any additional refrigerant needed based on page 5 of Module HVS Variable Speed Heat Pump Manual Charging Wiring Outdoor Unit Make all connections to the outdoor unit with rain tight conduit and fittings Most building codes require a rain tight disconnect switch at the outdoor unit as well alwa...

Страница 5: ...lar ducts A variance of 20 is allowable for sizing return ducts that connect to the RCM I or Hi Velocity Systems unit Where allowed by local codes a single return air grill may be used Note Return air grill must have equal minimum of free air area to return air Table 03 Return Air Duct Sizes Unit Rigid Ø Flex Ø Min Sq Inches Sq cm 50 51 52 12 305mm 14 356mm 120 774cm 70 71 12 305mm 14 356mm 120 77...

Страница 6: ... Connection Sizes Liquid Line Lq 1 2 13mm 1 2 13mm Suction Line S 7 8 22 3mm 7 8 22 3mm Drain Connection 3 4 M CPVC 19mm 3 4 M CPVC 19mm Access Ports Yes Yes Freeze Stat Yes Yes Shipping Weight 34 lbs 15 4 kg 47 lbs 21 31 kg Module Size L x W x H 19 3 8 x 10 1 8 x 18 1 2 492mm x 257mm x 470mm 25 3 8 x 10 1 8 x 18 1 2 645mm x 257mm x 470mm RCM I Specifications Refrigerant Cooling Module 2 Smaller c...

Страница 7: ...vel and only to the fan coil unit and module It does not include connections attachments and other products or materials furnished by the installer Terms and Conditions Any repair performed under warranty must be approved by Energy Saving Products Ltd for this warranty to be valid This warranty replaces all other warranties expressed or implied www hi velocity com Should there be multiple consecut...

Страница 8: ... complete with an in house test lab Energy Saving Products prides itself on Customer Service and provides design services and contractor support For all of your Heating Cooling and Indoor Air Quality needs the Hi Velocity System is the right choice for you Phone 780 453 2093 Fax 780 453 1932 Toll Free 1 888 652 2219 www hi velocity com Hi Velocity HE Z Fan Coils Green Technology Build Smart Breath...

Отзывы: