                             ENERGY KING™ Wood/Coal Boiler Owner’s Manual 

Š

 U. S.                 

Fuel Requirements 

 

BURN AIR-DRIED WOOD, OR ANTHRACITE OR BITUMINOUS COAL ONLY

 

 
 
 
 

It is important to use fuel that is clean, dry and consistent. Solid-fuel boilers, such as your ENERGY 
KING Wood/Coal Boiler, naturally produce ash as a byproduct of the burning process. Even with 
the ENERGY KING heating appliance’s highly efficient design, your heating appliance will still 
produce some amount of ash which will need to be cleaned periodically. The type and quality of fuel 
you burn affects the amount of ash produced and the performance of your heating appliance. To 
assist you in determining which fuel to use, here are some guidelines to consider: 

 

WOOD 

 
Burning wood for heat is as old as civilization itself. More than any other major fuel, wood provides 
us with energy independence – an easily available, locally produced and renewable source of heat 
on which we can rely.  

 

  The ENERGY KING Wood/Coal Boiler has 

been tested for operation with air-dried 
wood. 

 

  Wood should be seasoned (dried) for at 

least 12 months before burning. Properly 
seasoned wood should have about 20% - 
25% moisture content. To properly season 
wood, split the logs as soon as possible 
and loosely stack them in a dry spot for at 
least 12 months.  

 

You should not burn wet or green wood in 
your Boiler. Burning wet or green wood in 
your Boiler will not only reduce the 
efficiency of your appliance, but also 
increases the risk of dangerous creosote 
build-up in your appliance and chimney. 

 

  Softwoods, such as pine and fir, are easily 

ignited and burn rapidly with hot flames. 
With softwoods, you will spend more time 
reloading your ENERGY KING Wood/Coal 
Boiler, and will have much more difficulty 
achieving an overnight burn. For a longer 
lasting fire, it is best to use more dense 
hardwoods.  

 

  Ideally, you should burn a mixture of 

hardwoods and softwoods, using the hotter, 
faster burning softwoods to start your fire, 
and the denser hardwoods to maintain a 
longer-lasting fire.  

 

  With this in mind, choosing the kind of 

firewood that is best for you depends on 
what is available in your area. If hardwoods 
are unavailable in your area, you can 
control the burn rate by using larger pieces 
of wood. 

 

 

DO NOT BURN:

 Treated wood, colored 

paper, garbage, cardboard, solvents, or 
trash—burning these may result in toxic 
fumes, or produce soot and large flakes of 
char or fly ash. 

Burning treated wood, 

colored paper, garbage, cardboard, 
solvents or trash can be dangerous and will 
void your 

ENERGY KING

 warranty.

 

 

 

DANGER – Risk of Fire or Explosion

: Do 

not burn garbage, gasoline, naphtha, drain 
or engine oil, or other flammable liquids or 
inappropriate materials in this heating 
appliance. 

 

 

Storage

 

  Store all fuel in a dry location away from 

the elements. Never burn wet or green 
wood. 

 

  Do not store fuel within the heating 

appliance installation clearances or within 
the space required for refueling, ash 
removal and other routine maintenance 
operations. 

Risk of Fire:  Do not store fuel or other combustible 
material within the marked installation clearances. 

Содержание 35EK-D

Страница 1: ...Coal Boilers Models 35EK D 45EK D ASME Certified Model A40EK D Installation Operation Maintenance Manual RJM Manufacturing Inc 1875 Olson Drive Chippewa Falls WI 54729 715 720 1794 Fax 715 720 1797 ww...

Страница 2: ......

Страница 3: ...is the owner s responsibility to make certain that both the appliance and installation are acceptable to their insurance company as well as ensuring compliance with all local state and national codes...

Страница 4: ......

Страница 5: ...e to cool before servicing Never fire a boiler that is low on water Never add water to a hot boiler The fuel loading and ash removal doors must be closed tightly during operation All seals must be mai...

Страница 6: ...nated areas A working smoke detector must be installed in the same room as this heating appliance For additional safety RJM Manufacturing Inc also recommends installing working smoke detectors and a l...

Страница 7: ...mney 18 Chimney Connector 18 Barometric Draft Control 19 PLUMBING 20 OPERATION 22 GENERAL INSTRUCTIONS 22 GATE VALVES 22 FIRST FIRE 23 TYPICAL OPERATION CYCLE 23 OVERFIRE 24 POWER FAILURE INSTRUCTIONS...

Страница 8: ...Rev 08 24 10 ENERGY KING Wood Coal Boiler Owner s Manual U S 2 This page is intentionally left blank...

Страница 9: ...D 30 x 17 x 30 30 x 17 x 30 30 x 17 x 35 Burn Chamber Volume 8 5 cu ft 8 5 cu ft 10 cu ft Log Length 26 26 32 Sliding Smoke Baffle Standard Standard Standard Cast Iron Fuel Loading Door Size H x W 15...

Страница 10: ...to the Boiler Draft is the force that moves air from the burn chamber up through the chimney See Venting for further instructions 2 Sliding Smoke Baffle When open the sliding smoke baffle allows smok...

Страница 11: ...icks protect the sides of the Boiler s burn chamber ENERGY KING A40EK D Boilers and 35EK D Boilers use 12 firebricks 6 on each side The ENERGY KING 45EK D Boiler uses 14 firebricks 7 on each side 9 As...

Страница 12: ...hout the world The core values of ASME are rooted in its mission to better enable mechanical engineering practitioners to contribute to the well being of humankind About Codes Standards What is a stan...

Страница 13: ...l factory built chimney Do not connect this unit to any chimney flue serving any other appliance See Venting for further instructions b Has your chimney been inspected For your safety it is important...

Страница 14: ...also increases the risk of dangerous creosote build up in your appliance and chimney Softwoods such as pine and fir are easily ignited and burn rapidly with hot flames With softwoods you will spend m...

Страница 15: ...id fuel heating appliance and its components If you choose to burn bituminous coal be sure to select only high grade bituminous coal Coal Size Your ENERGY KING Wood Coal Boiler is designed to use coal...

Страница 16: ...ay from the boiler when no other zones are calling for heat In this way it will prevent your ENERGY KING Wood Coal Boiler from overheating However as a safety feature if your Boiler should overheat or...

Страница 17: ...NG Wood Coal Boiler in an add on application locate the ENERGY KING Wood Coal Boiler as close to the new or existing chimney as possible and as close to your existing boiler as practical However a min...

Страница 18: ...er to promote the most efficient combustion for either fuel The words Wood and Coal are cast into the hearth plates on opposite sides a If you are going to burn wood position the hearth plates with th...

Страница 19: ...and secure using the bolts found on the draft opening 7 Pressure Temperature Gauge Insert the Pressure Temperature Gauge into the right front receptacle located on top of the Boiler 8 Pressure Relief...

Страница 20: ...t the upper left on the back of the ENERGY KING Wood Coal Boiler model 35EK D or 45EK D b Apply pipe joint compound not included to the threads of the 4 domestic hot water coil c Insert the 4 domestic...

Страница 21: ...ll installations it may be necessary if The heating appliance does not draw steadily smells experiences smoke roll out burns poorly or backdrafts whether or not there is combustion present Any of the...

Страница 22: ...d to be sure it is clean and free from defect or damage All connections must comply with NFPA Standard 211 and all applicable building codes and regulations When installing a factory built chimney fol...

Страница 23: ...ney must be at least 3 feet higher than the highest point where it passes through the roof and at least 2 feet higher than the highest part of the roof or structure that is within 10 feet of the chimn...

Страница 24: ...upport hangers or brackets every three feet if it is absolutely necessary to have a run of more than six feet which is not recommended Chimney connector sections must be attached to the heating applia...

Страница 25: ...fuel heating appliance burn chamber A pivoted counterbalanced flap is pulled open by the draft when the draft reaches a critical amount This permits air to enter the chimney thus preventing the draft...

Страница 26: ...nsion tank is properly sized Auto Fill In order for a pressurized hot water heating system such as the ENERGY KING Wood Coal Boiler to function safely and efficiently it must be filled with water at a...

Страница 27: ...r the pressure relief valve which will release water thus relieving pressure RJM Manufacturing Inc recommends installing a normally open zone valve and a strap on non immersion surface mounted aquasta...

Страница 28: ...ys add water to a boiler gradually Never add water to a hot appliance For greatest efficiency you may sometimes need to allow your existing conventional heating system to assist your ENERGY KING Wood...

Страница 29: ...of your ENERGY KING Wood Coal Boiler Some odors may be given off a new ENERGY KING Wood Coal Boiler during the initial few hours of burning while the steel and the paint are being cured Ventilating th...

Страница 30: ...l trigger the pressure relief valve and release water to relieve pressure If this should occur allow the Boiler to cool completely before refilling Never fire a boiler that is low on water Never add w...

Страница 31: ...minutes for the fire to establish itself Once you have some red hot burning embers add larger pieces of wood a Vary the position of the wood in the burn chamber to maximize the exposed surface area o...

Страница 32: ...grates Removal of the coal ash will allow for passage of primary air to the coal bed and prevent damage or warpage to the grates 4 A coal fire should not be poked or broken up as this tends to bring...

Страница 33: ...oal Boiler to operate with draft controls fully open for approximately 15 minutes or until the fresh coal ignites When the coal is properly ignited adjust the thermostat accordingly Check the fire per...

Страница 34: ...al on the grate in front of the banked coal Be careful not to smother your existing coals 6 Close the fuel loading door and sliding smoke baffle Banking Banking allows you to recharge your coal fire i...

Страница 35: ...e monthly during the heating season to determine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire Be aware that the hotter the f...

Страница 36: ...operate at peak performance Failure to clean and maintain this Boiler as indicated can result in poor performance and safety hazards Please use Appendix D Purchase Service Record to keep a record of y...

Страница 37: ...e the entire ENERGY KING Wood Coal Boiler a thorough cleaning Your venting system should be inspected and cleaned annually Clean and remove fly ash from chimney connector flue pipes and chimney Soot b...

Страница 38: ...only high quality clean dry fuel as outlined in Fuel Requirements Improper Draft Too little or too much draft Insufficient combustion air Solution Adjust the draft controls and observe until you deter...

Страница 39: ...azy or dirty or startup is slow or smoky Your exhaust or combustion air systems may be blocked Verify all vents and pipes are free from obstruction and the draft controls are operating correctly Your...

Страница 40: ...ightly and all gaskets are in good condition Your exhaust or combustion air systems may be blocked Verify all vents and pipes are free from obstruction and the draft controls are operating correctly Y...

Страница 41: ...KING Wood Coal Boiler requires frequent refilling Your Pressure Relief Valve may be installed incorrectly or may be faulty Please contact your ENERGY KING dealer or heating contractor Check for leaks...

Страница 42: ...Rev 08 24 10 ENERGY KING Wood Coal Boiler Owner s Manual U S 36 This page is intentionally left blank...

Страница 43: ...Rev 08 24 10 ENERGY KING Wood Coal Boiler Owner s Manual U S 37 Appendix A Wiring Diagram...

Страница 44: ...Rev 08 24 10 ENERGY KING Wood Coal Boiler Owner s Manual U S 38 This page is intentionally left blank...

Страница 45: ...Manufacturing Inc recommends installing a series of three gate valves The three gate valves are to be used in the event you do not use your ENERGY KING Wood Coal Boiler for an extended period one or m...

Страница 46: ...Rev 08 24 10 ENERGY KING Wood Coal Boiler Owner s Manual U S 40 This page is intentionally left blank...

Страница 47: ...ription 4 DRA FD BOX BOIL Forced Draft Parts Box 4 DRA FDTUBEASSY Forced Draft Blower Tube Assembly 4 ELE CTRLBX FD B Control Box Assembly 4 ELE 24VTHERMOST 24 Volt Wall Thermostat 4 ELE AQUASTAT Aqua...

Страница 48: ...s 6 required 4 CAS SHFRAME480 Shaker Grate Frame for Optional Shaker Grates 2 required 4 CAS SPACERGR45 Spacer Grate for 45EK D 4 CAS SHGRHNDL Shaker Grate Handle for Optional Shaker Grates 4 HAN 1 2C...

Страница 49: ...g Handle for Ash Removal Door Sliding Smoke Baffle and Optional Shaker Grates Handles 4 HAN 5 8CHROME 5 8 Chrome Spring Handle for Fuel Loading Door Handle 4 HAR DOORPIN Door Pins 4 Required 2 per doo...

Страница 50: ...Rev 08 24 10 ENERGY KING Wood Coal Boiler Owner s Manual U S 44 This page is intentionally left blank...

Страница 51: ...ft side of the unit Have you completed returned your warranty card Date Mailed Has Dealer Installer gone over the operation and maintenance of appliance Purchase Installation Record MODEL SERIAL NUMBE...

Страница 52: ...ted in the Appendix of your Owner s Manual Without this information we will not be able to complete your requested warranty claim Once we receive your completed Warranty Claim Form and Warranty Regist...

Страница 53: ...ON ADDRESS 1 ADDRESS 1 ADDRESS 2 ADDRESS 2 CITY ST ZIP CITY ST ZIP TELEPHONE TELEPHONE FAX EMAIL Model Serial No Date of Purchase Date of Failure Date of Repair Description of Failure Repairs Made ple...

Страница 54: ...Rev 08 24 10 ENERGY KING Wood Coal Boiler Owner s Manual U S 48 This page is intentionally left blank...

Страница 55: ...ol box the Aquastat Immersion control pressure relief valve and pressure temperature gauge What is covered by this warranty This warranty covers any defects in materials or workmanship in your new ENE...

Страница 56: ...ncidental or consequential damages or limitation of implied warranties so the limitations or exclusions in this limited warranty may not apply to you NO EMPLOYEE OR REPRESENTATIVE OF RJM MANUFACTURING...

Страница 57: ...S 51 Supplement A Aquastat Immersion Control The following document was prepared and published by Honeywell International for distribution with their models L4081A B and L6081A C Multiple Aquastat Con...

Страница 58: ......

Страница 59: ......

Страница 60: ......

Страница 61: ......

Страница 62: ......

Страница 63: ......

Страница 64: ......

Страница 65: ......

Страница 66: ......

Страница 67: ......

Страница 68: ......

Страница 69: ......

Страница 70: ...24 V Wall Thermostat The following document was prepared and published by Honeywell International for distribution with their models T822K L T827K wall thermostats It is reproduced here for reference...

Страница 71: ......

Страница 72: ......

Страница 73: ......

Страница 74: ......

Страница 75: ......

Страница 76: ......

Отзывы: