Resolute Gas Heat – Sixth Edition – September, 2018
23
DIGITAL MANAGER OPERATION
WARNING: Do Not Jump!
If you apply 24VAC to any digital sensor lead
with the sensor connected to the Manager,
you will burn out both the sensor and the
Manager in less than a second.
NOTE: The Manager cannot lockout the
primary control on the burner. The 140
°
F light
flashing will usually indicate that a burner
lockout has occurred.
Testing Manager Lights:
To confirm operation
of the Manager lights, turn power off briefly and
power up the Manager. On startup, all outputs
and temperature lights will turn on for a brief
moment.
A) Thermostat Lights:
Indicate a thermostat calling for heat. If all lights are OFF, the burner will not run because there is no call for heat. T
4
is located on the bottom. SET HEAT ANTICIPATORS FOR 0.1 AMPS.
B) Digital Temperature Sensor
:
Senses return temperature and is required for manager to work properly. 100°F light flashes if sensor is not
communicating with Manager properly and indicates that the Manager is operating in “Service Board Mode”.
C) Monitor Contacts:
For connection to System Monitor or security systems are located here.
D) Option Switches:
Used to customize system settings.
Set option switch 2 to ON for sidewall vent systems.
E) Temperature Display:
Indicates boiler RETURN temperature, not supply temperature.
The Manager is the
operating aquastat
and will turn off the burner if
return
temperature reaches 170°F
(operating limit).
With option switch 1 turned on for systems with gas burners, the zone outputs will open when the return
temperature is above 150° F and close zone outputs when the return temperature drops below 130° F. If a new
zone calls when the returns are below 150° F the new zone will not open until the temperature exceeds 150° F
(even if other zones are open).
The boiler will typically take about 90 seconds to reach 150° F from a cold start
.
When the Manager is working properly and has found a condition that needs service, the 100º, 120º, 130º, or
140º light will flash. See page 32.
F) Heating or Zone Lights:
Indicate 24-volt power from 24VAC to Z
X
(Z
HW
, Z
1
, Z
2
, Z
3
, and Z
4
). This provides power to 24-volt zone valves or zone
circulator relays. NEVER JUMPER THIS CONNECTION!
G) Inducer Light On:
Indicates 24 volts from IND to 24VAC. This pulls in the 24-volt coil on the inducer relay, providing 120-volts to the
power vent.
This will only operate with option switch 2 ON.
H) Burner Light On:
Indicates a closed contact between B
1
to B
2
. This is wired to T-T on the burner primary control.
If the burner light goes off, it will delay restart for two minutes to prevent short-cycling the burner. (45 seconds for a
Zone HW call).
I)
Circulator Light:
On indicates 24 volts from manager CIRC to manager 24VAC. This pulls in the 24-volt coil on the Burner/Main
circulator relay, providing 120-volt power to both the main circulator and the burner.
A
B
C D
E
I
H
G
F
Содержание Resolute Boiler
Страница 2: ......
Страница 36: ...Resolute Gas Heat Sixth Edition September 2018 34 This page intentionally left blank ...
Страница 37: ...Resolute Gas Heat Sixth Edition September 2018 35 This page intentionally left blank ...
Страница 38: ...Resolute Gas Heat Sixth Edition September 2018 36 This page intentionally left blank ...
Страница 39: ...Resolute Gas Heat Sixth Edition September 2018 37 This page intentionally left blank ...
Страница 40: ...Resolute Gas Heat Sixth Edition September 2018 38 This page intentionally left blank ...