Page 24
Fault Finding.
F1
A:
Does the power circuit for the Enerdrive ADV-BMS Relay driver have a 10amp fuse in it?
B:
Check polarity of the “Power Input” in the Advanced BMS Relay Driver. If it is Reverse Polarity you will need to replace the Advanced Relay
Driver as internal damge has occurred.
F2
Check that all wires are connected between the Blue Sea Latching Relay and the Advanced Relay driver if this is correct and LED still does not light
up - call Enerdrive.
F3
Make sure the connector is completely removed. If LED does not go out - Call Enerdrive.
F4
A:
Check that all wires are connected between the Blue Sea Latching Relay and the Advanced Relay driver.
B:
Does the Advanced Relay Driver still have power?..Check the fuse.
F5
A:
Make sure wire is connected correctly.
B:
If all wiring is ok - Call Enerdrive.
F7
If Input 3 LED is out and the Red LEDs on TOR Outputs 1-4 and Outputs 1-2 are NOT ON - Call Enerdrive.
If Input 3 LED does not turn on - call Enerdrive.
F8
If there are no Red LEDs turned on - call Enerdrive.
F9
A:
Check that the EN3TOR-G2 sensor lead is connected to the Temp Port on the Enerdrive AC Charger and connected to one of the TOR Ports on
the Advanced Relay Driver.
B:
Check that the EN3TOR-G2 sensor lead is connected to the Temp Port on the Enerdrive DC2DC Charger/s and connected to one of the TOR ports
on the Advanced Relay Driver.
C:
Check that the SR-TS-TOR-G2 sensor lead is connected to the Temp Port on the TriStar Controller and connected to a TOR Port on the Advanced
Relay Driver.
D:
Check that there is a twin core cable between the Combi Trigger 1 INPUT & COM contact and into the NO/COM contact on OUTPUT 1 or 2 on
the Advanced Relay Driver.
F10
If fault codes are still active, you may still be within the 10 minute “Stop Charge” program. Wait a further 10 minutes and if the fault codes don’t
disappear - call Enerdrive.
F11
If any of the charge sources are still in fault code, check sensor cable from Advanced Relay Driver to charge source. If connected correctly and fault
is still active - call Enerdrive.
F12
C:
If all wiring is ok - Call Enerdrive.
Please note: If using the Combi Temp Sensor for Cabinet Fan operation from Program Relay 2 as per diagram, please connect this sensor and the
EPC-TOR sensor lead into a 6C6P Splitter Box as shown on the wiring diagram.