To Install & Commission Your Lithium System Please Complete The Following Steps.

FOR USE WITH ALL SYSTEM INSTALLATIONS

1.  Prior to Installationplease make sure you have the correct wiring diagram for your installation and the Main Battery 

Latching relay is in the OFF Position (Yellow button flush with the top of the switch).

2. Make sure the Dip Switch on the right hand side of the Enerdrive ADV-BMS Relay Driver is set to Program A.
3. Leave the main battery cables disconnected until complete.
4. Connect all  DC & AC cables for the system taking note that the polarity is correct, Especially on the BMS Relay Driver.
5. All Positive DC cables for DC LOADs & Inverters are to be on the “SYSTEM” side of the Main Battery Latching Relay.
6. All Positive DC cables from the Enerdrive approved battery chargers & Tristar Solar to be installed on the “BATTERY”

side of the Main Battery Latching Relay.

7.  Make sure all High & Low protection cables to the Advance BMS Relay Driver from the Battery, Battery Monitor and

all charging devices have been installed as per wiring diagram.

8. Make sure all High & Low protection cables to the Advance BMS Relay Driver from both the Battery & Battery Monitor

have been installed as per the wiring diagram.

9.  Connect DC Cables to the Battery. 

LITHIUM COMMISSIONING CHECK SHEET

Refer Fault Finding Codes 1 Thru 11 Refer To Enerdrive Advanced Relay Driver And

Charging Sources.

YES

NO

1

On activating the Long Term Storage Switch, does the GREEN – DC Power, Input 1,2,3 LEDs on the BMS 

Relay Driver come on?

see: F1

Engage the Main Battery Latching Relay – does the GREEN LED for the “Latching Relay” come on? 

Please Note: If using an ePRO Combi Inverter/Charger, switch the rocker switch on the front of the unit to the ON position (number 1)

Please Note: The 10 minute “stop charge” program is now engaged. Questions 8 thru 10 to be completed within the 10min program.

Please Note: If using an ePRO Combi Inverter/Charger, Output 3 LED will still be on (RED) for an additional 30mins to keep the inverter

“Locked Out”. The “Inverter” LED on the front of the Combi unit will show RED? 

Remove the connector from Input 1 –the Green LED for Input 1 will now be off and the Status LED will start 

flashing GREEN?

see: F2

3

see: F3

4

After a 40s delay, all TOR Outputs and Outputs 1-3 LEDs will come on (Red) and disengage all connected sources. 

Within a further 15s, the Main Battery Latching Relay will disengage.  Within a further 10s all TOR Outputs and

Outputs 1 & 2 LED’s will go out turning all connected sources back on? Output 3 LED will still be on (RED) for an 

additional 30mins to keep a connected ePRO Combi inverter “Locked Out”  to allow for the battery to charge 

before inverter use is possible. If an ePRO Combi is fitted, the “Inverter” LED on the front of the Combi unit should 

show RED?

see: F4

5

Replace the connector back into Input 1 –the GREEN LED for Input 1 will turn on. If so, remove the DC Power 

Input connector on the Advanced Relay Driver and re-insert to reset the Advance Relay Driver to bypass the 

30min delay on the inverter lock out to continue the commissioning process and re-engage the Main Battery 

Latching Relay.

see: F5

6

Input 2 commissioning process is the same as Input 1. Follow steps 3/4/5/ for Input 2 before proceeding to Step 7.

7

Remove the connector from Input 3 – the Status LED will be now flashing Red and the Green LED for Input

3 will now be off? 

see: F7

8

Did all TOR Outputs and Output LED’s 1-2 turn on RED?  

If using an Enerdrive ePOWER AC charger – (Fault Code – E06)

If using an Enerdrive DC2DC charger – (Fault Code – E07)

If using Morningstar Tristar - Fault Code - LEDs on the front of the controller will be flashing Red/Green

If using an ePRO Combi Inverter/Charger, did the Combi “Charger” LED Turn RED

see: F8

see: F9A

see: F9B

see: F9C

see: F9D

9

Do all connected charge sources show a Fault Code on their respective screens?

    

Содержание Lithium Power Pack Series

Страница 1: ......

Страница 2: ...ging sources solar vehicle and the inverter charger before disengaging the main battery relay turning off the whole electrical system to protect the battery The program will then switch on the signal...

Страница 3: ...e Mode but you will have no temperature control on the system thus leaving the lithium protection system compromised Contact Enerdrive to arrange for a replacement Temperature Sensor PROGRAM B The Ene...

Страница 4: ...10 Amps Max programmed to switch trigger contacts relays connected to Alternators Chargers Solar or DC AC relays cabinet cooling fan and Combi Inverter Charger Units Hi Low Alarm Protection 1 x Tempe...

Страница 5: ...isabling connected charge sources When Green LEDs are on all input circuits are within range and operating correctly When one or more Green LEDs are out the input is receiving an alarm signal from the...

Страница 6: ...e ePRO Plus battery monitor can measure DC currents up to 600Amps 500Amp continuous and voltages up to 70Vdc So any lead or lithium based battery from 12V up to 48V can be monitored A Blue Sea 500amp...

Страница 7: ...testing over the last 6 years the Enerdrive Lithium battery standing voltage when fully charged with no loads running will be between 13 35v 13 45v at 100 capacity When discharged to near 25 capacity...

Страница 8: ...store your vehicle vessel under cover and you don t have access to AC power then you must prevent the battery from being discharged to a critical potentially non recoverable state of charge Before you...

Страница 9: ...Page 9...

Страница 10: ...Page 10 Power Input 1 Input 2 Input 3 Input 4 if connected Latching Relay...

Страница 11: ...3 on the Advanced BMS Relay Driver are Green and the battery monitor is 26 or higher in capacity A This has happened because the system has registered 1 of 2 faults 1 A high temperature condition has...

Страница 12: ...ttery Connection Balancer Link N A Lithium Setup ePOWER Single 12v 2018 G2 SR TS TOR G2 TOR Output SR TS TOR G2 Wire to RTS Terminal 2 1 1A 10A NOTE Long term storage switch Only turn this switch OFF...

Страница 13: ...inet Fan Output 4 Turns on when Temp Sensor 35 C EN3TOR G2 Plug into BTS EN3TOR G2 Plug into BTS GREEN BLUE BLACK RED WHITE YELLOW EPL ABS Battery Battery Battery Battery RED BLUE WHITE YELLOW GREEN B...

Страница 14: ...lease call Enerdrive on 07 3390 6900 Temp Sensor 5A Optional Cabinet Fan Output 4 Turns on when Temp Sensor 35 C EN3TOR G2 Plug into BTS Battery Battery RED BLUE WHITE YELLOW GREEN BLACK EPL ABS Volta...

Страница 15: ...Cabinet Fan Output 4 Turns on when Temp Sensor 35 C EN3TOR G2 Plug into BTS Battery Battery RED BLUE WHITE YELLOW GREEN BLACK EPL ABS Voltage Protection Circuit Battery Connection Balancer Link N A 2...

Страница 16: ...ttery Battery RED BLUE WHITE YELLOW GREEN BLACK RED BLUE WHITE YELLOW GREEN BLACK EPL ABS Voltage Protection Circuit Battery Connection Balancer Link N A Voltage Protection Circuit Battery Connection...

Страница 17: ...RED BLUE WHITE YELLOW GREEN BLACK RED BLUE WHITE YELLOW GREEN BLACK EPL ABS Voltage Protection Circuit Battery Connection Balancer Link N A Voltage Protection Circuit Battery Connection Balancer Link...

Страница 18: ...ata warranty applicable to original end user only Enerdrive does not warrant the battery for use in any residential system sold with the intent or purpose The Enerdrive ePRO Plus battery monitor that...

Страница 19: ...undercharging charging or installing in reverse polarity improper maintenance allowing the battery to be deeply discharged via a parasitic load or mishandling of the battery such as but not limited t...

Страница 20: ...ctive unit that is returned to Enerdrive within 30 days of the date of purchase will be replaced free of charge If such a unit is returned more than 30 days but less than two years from the purchase d...

Страница 21: ...te stopcharge programisnowengaged Questions8thru10tobecompletedwithinthe10minprogram PleaseNote IfusinganePROCombiInverter Charger Output3LEDwillstillbeon RED foranadditional30minstokeeptheinverter Lo...

Страница 22: ...down the charging sources After 10mins from initiation did all TOR Outputs and Outputs 1 2 LED s turn off and did all connected charge source Fault Codes disappear If you have answered YES to all que...

Страница 23: ...nsor lead is connected to the Temp Port on the Enerdrive AC Charger and connected to one of the TOR Ports on the Advanced Relay Driver B Check that the EN3TOR G2 sensor lead is connected to the Temp P...

Страница 24: ...Page 25 NOTES...