Enerdrive ePRO COMBI Owners Manual
Parameter
AC Input Power Boost
Value
Off
Description
AC Input Power Boost temporarily assists weak AC input sources when the
connected load needs more power than available from the grid or generator.
This is accomplished by running the inverter in parallel with the AC input source.
The inverter can add power up to it’s nominal output power rating assuming the
battery is healthy. This parameter can be set On or Off.
Configurable by
DIP switch (DIP 7) and Dashboard
Parameter
Ground switch
Value
Enabled
Description
The ground switch is an internal relay that automatically connects AC output
Neutral (N) to Protective Earth (PE = chassis) in inverter mode. This enables the
use of a ground fault circuit interrupter (GFCI) at the AC output of the ePRO
Combi. When a non-grounded (floating-) output is required, this Parameter can
be disabled.
Configurable by
Dashboard
Parameter
AC input fail sensitivity
Value
Normal
Description
This parameter can be set to Very Low, Low, Normal, High and Very High. The
value of this Parameter decides how fast the ePRO Combi detects a signal fail
at the AC input. The lower settings are resulting in a slower AC input source
g
inverter transfer time, while the higher settings result in the fastest transfer times.
The settings Low and Very Low can be used when the AC input signal is distorted
or unstable, which could be the case when a small generator is used. The settings
High and Very High can be used when the ePRO Combi is connected to a solid grid
or quality generator. The factory setting Normal is a good compromise, which still
results in a fast AC input source
g
inverter transfer time of less than 5ms, while
being reasonably immune against distorted AC input signals.
Configurable by
Dashboard
Parameter
Battery type / Charge program
Value
AGM
Description
The default charge program AGM is compatible with typical AGM type batteries,
but can be used for other types of lead-acid batteries as well. Please make sure
that you always check if the ePRO Combi charge program settings, are compatible
with the used battery! The AGM charge program absorption voltage is 14.3V
(28.6V@24V) and the float voltage is 13.3V (26.6V@24V). Other selectable charge
programs are Flooded, GEL and Custom. For further charge program information,
please see chapters 3.3 and 5.1.
Configurable by
DIP switch (DIP 5 and 6) and Dashboard