So how does the “Advance Enabled Setting” operate? 

If a battery cell goes “Hi Voltage” and “opens” the hi voltage loop wire, then the Advanced BMS Relay Driver 
will activate the output contacts that will drive the installed relay/contacts to cut out all charging sources (solar/
vehicle/main charger) for 10 minutes. If the cell has not come back within range before 10 minutes, it will stay 
active for another 10 minutes and repeat until the cell/s are within range. This setup allows the system loads to 
still be powered.
If the ePRO Battery monitor sees a LOW SOC% or overall low voltage, then the main battery relay will trip out. 
You will need to start a charging source and re-engage the main battery relay by pressing in the Yellow button 
on top of the main battery relay. The Advanced BMS Relay Driver will turn the main battery relay OFF every 
6min if the SOC% on the battery monitor is still below the set point. So this may need to be reset a few times 
before the SOC% set point reaches it re-engagement point.

Main Battery Relay

 PLEASE NOTE

The battery has a self-discharge rate of 5% per month @ 25°C.  When storing the battery with the main 
latching relay disengaged, the ePRO Battery Monitor and Advance Relay Driver will still be powered, adding 
a further drain on the battery.
It is the responsibility of the end user to maintain the battery in a charged state. The battery should not be 
left for more than 30 days without checking its charge state. Enerdrive recommend that a battery left in a 
“storage state” should be checked and charged as often as possible (maximum 30 days) to maintain maximum 
life expectancy of the battery.  Failure to follow these requirements will see an early failure of the battery 
which is not covered under warranty.

Содержание EPL-100AH-12v-BATT

Страница 1: ...Lithium Ion Battery System Owner s Manual V1 0 1 2015 Lithium Power Pack...

Страница 2: ...a tank and even to the extent of being a little bit overkill on the packaging and protection So how does our system actually work The Advance BMS relay driver is designed to take a loop signal wire fr...

Страница 3: ...elay The Advanced BMS Relay Driver will turn the main battery relay OFF every 6min if the SOC on the battery monitor is still below the set point So this may need to be reset a few times before the SO...

Страница 4: ...s Amp hours Percentage State of Charge Time to go It will also record all of the history data of the Lithium battery Deepest Discharge Battery Cycles Hi Low Voltage Amps All Alarm History Etc This is...

Страница 5: ...2 90v 13 00v As you can see here the voltage variance between 100 full and 25 full is only 0 55v This is quite different to lead acid batteries where voltage can range from 12 72v at 100 to 11 88v at...

Страница 6: ...n battery switch and start turning on your loads Keep charging sources connected until the battery reaches maximum charge 100 Q What if I see red lights on on the outputs of the Advance Relay Driver B...

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ...that is standard with every Lithium Ion battery kit is pre programmed by Enerdrive to suit the battery configuration Any changes that are made to the pre configuration programming of the ePRO meter wi...

Страница 12: ...nals for lifting or carrying the battery Charging sources that do not have programmable lithium profile configurations and charge voltage between 13 5V and 14 5V no lower than 13 0V and no higher than...

Страница 13: ...or at its option replace it free of charge If the unit is repaired new or reconditioned replacement parts may be used at manufacturer s option A unit may be replaced with a new or reconditioned unit o...

Отзывы: