To troubleshoot the unit, please note the error code displayed on the main unit and review
“Understanding the Error Codes” in this section.
Problem
Possible Cause/Condition
Solution
No AC Output. All the
LEDs and the display
are off.
The unit is turned off.
Note:
The power button On/Off action takes
place at its release moment and after a “beep”
is heard
Turn the unit ON by pressing the “Power”
button (when the unit is in Battery/inverter
mode, or in By-Pass mode if the PS4 parameter
is set) otherwise the unit should always turn
on automatically at the moment the AC-Input
power is connected.
No power coming into the unit
Check the battery DC fuse, the Disconnect
Switch (if installed), the AC Input Source and
the AC Input Branch Breaker is either tripped or
turned OFF
No AC output on the
front GPO or the side
IEC-C19 socket and the
Status LED is Green or
Amber
The units thermal breaker/s and or RCD has
tripped.
Check AC loads and reset the thermal breakers
and or RCD.
AC Output turns ON
and OFF.
Power Safe mode (“PS2”) enabled and AC load
<10W
The load connected must be below the AC load
sense threshold of 10W +/-25%
No AC Output. Status
LED is red
The unit has shutdown, check Error code shown
on display.
Verify the error condition and make correction
During AC Input
Power Outage, there
is no AC Output power
when battery power
is available.
The unit is set to “Non-Backup” mode (“PS0”)
and AC Input Power is not available.
Change the “PS0” setting to a different setting if
you want to turn the inverter ON.
With “PS0” setting, the inverter is completely
OFF. When the AC Input Power is not available
and the “Power” button is pressed once, the
display and LEDs stay working for about 30 sec
only. With this setting, the unit will provide AC
Output Power only when the AC Input Power is
available.