Installation Instructions and Owner’s Manual

Unvented LP-Gas Vent Free Room Heaters

WARNING:

 This appliance requires a 3/8” NPT 

(National Pipe Thread) inlet connection to the 

pressure regulator. Use of floor mounting feet will 

require you to use a 3/8 NPT street elbow to make 

gas connection. 

CAUTION:

 Never connect heater directly to the Propane 

supply. This heater requires an external regulator (not 

supplied).  Install  the  external  regulator  between  the 

heater and Propane/LP supply. 

The installer must supply an external regulator. The ex

-

ternal regulator will reduce the incoming gas pressure 

to between 11 and 14 inches of water. If you do not 

reduce incoming gas pressure heater regulator dam

-

age could occur. Install external regulator with the vent 

pointing down. Pointing the vent down protects it from 

freezing rain or sleet.

CAUTION:

 Use only new black iron or steel pipe. 

Internally-tinned copper tubing may be used in cer

-

tain areas. Check your local codes. Use pipe of larger 

enough diameter to allow proper gas volume to heater. 

If pipe is too small, undue loss of pressure will occur. 

Installation must include an equipment shutoff valve, 

union and plugged 1/8” NPT tap. Locate NPT tap within 

reach of test gauge hookup. NPT tap must be upstream 

from heater (see figure 12).

Figure 12

*A CSA/AGA certified equipment shutoff valve with 

1/8” NPT tap is an acceptable alternative to test gauge 

connection. Purchase the CSA/AGA certified equipment 

shutoff valve from your dealer. 

IMPORTANT:

 Install an equipment shutoff valve in an 

accessible location. The equipment shutoff valve is for 

turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male threads. This will 

prevent excess sealant from going into pipe. Excess 

sealant in pipe could result in clogged heater fuel train.

Pressure 

Regulator

Heater 

Cabinet

Ground Joint Union

Equipment 

Shutoff Valve

From regulated LP tank 

(11” W.C. to 14” W.C. 

Pressure)

Tee Joint

1/8” NPT Plug Tap

Cap

Pipe Nipple

Tee Joint

3/8” NPT Pipe Nipple

Sediment 

Trap

Test Gauge 

Connection

Reducer Bushing 

to 1/8” NPT

3” Minimum

CAUTION:

 Use pipe joint sealant that is resistant to 

LP-Gas

Install sediment trap in supply line as shown in figure 

12. Locate sediment trap where it is within reach for 

cleaning. A sediment trap traps moisture and con

-

taminants. This keeps them from going into heater. If 

sediment trap is not installed or is installed improperly, 

heater may not run correctly.

IMPORTANT:

 Hold pressure regulator with wrench 

when connecting it to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

WARNING:

 Test all gas piping and connections for 

leaks after installing or servicing. Correct all leaks 

at once. 

WARNING:

 Never use an open flame to check for 

a gas leak. Apply a mixture of liquid soap and water 

to all joints. Bubbles forming show a leak. Correct 

all leaks at once. 

PRESSURE TESTING GAS SUPPLY PIPING 

SYSTEM

Test pressure in Excess of ½ psig (3.5kPa)

1.  Disconnect appliance with its appliance main 

gas valve (control valve) and equipment shutoff 

valve from gas supply piping system. Pressures 

in excess of ½ psig will damage heater regula

-

tor.

2.  Cap off open end of gas pipe where equipment 

shutoff valve was connected.

3.  Pressurize supply piping system by either using 

compressed air or opening main gas valve on 

or near gas meter.

4.  Check all connections and joints in gas supply 

piping system. Apply mixture of liquid soap and 

water to gas joints. Bubbles forming show a 

leak.

5.  Correct all leaks at once.
6.  Depressurize and relieve pressure in supply 

piping system.

7.  Reconnect heater and equipment shutoff valve 

to gas supply. 

8.  Reconnected fittings must be checked for leaks 

in next section. 

Test Pressure Equal To or Less Than ½ psig (3.5 kPa)

1.  Close equipment shutoff valve (see figure 13).
2.  Pressurize supply piping system by either using 

compressed air or opening main gas valve on 

or near gas meter.

3.  Check all joints from the gas meter to equip

-

ment shutoff valve (see figure 14). Apply 

mixture of liquid soap and water to gas joints. 

Bubbles forming show a leak.

Содержание HSVFB20LPT

Страница 1: ...ovisions for adequate combustion and ventilation air must be provided Refer to Fresh Air for Combustion and Ventilation section on page 4 of this manual WARNING Improper installation adjustment altera...

Страница 2: ...hildren and adults away from hot surfaces to avoid burns or clothing igni tion Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young children should be c...

Страница 3: ...6 3 Keep all air openings in heater clear free of debris or any blockage This will insure that enough air for proper combustion enters the heater 4 If heater shuts off do not relight until you provide...

Страница 4: ...l Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Com bustion and Ventilation All spaces in homes fall into one of the three following ventilation classifications 1 Unusually Tight Construction 2 Unc...

Страница 5: ...Vent Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can support 6...

Страница 6: ...pos sible provide greater clearances from the floor ceil ing and joining walls WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh ai...

Страница 7: ...ll be located Make sure mounting bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provid...

Страница 8: ...bottom mounting screw into wall stud drill holes at marked locations using 9 64 drill bit 5 Re place heater onto mounting bracket 6 Place spacers between bottom mounting holes and wall anchor or drill...

Страница 9: ...o 14 W C Pressure Tee Joint 1 8 NPT Plug Tap Cap Pipe Nipple Tee Joint 3 8 NPT Pipe Nipple Sediment Trap Test Gauge Connection Reducer Bushing to 1 8 NPT 3 Minimum CAUTION Use pipe joint sealant that...

Страница 10: ...TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the...

Страница 11: ...t cleaning due to excess lent from carpeting bedding material pet hair etc Make sure grille guard is in place before running heater If screen or grille guard is removed for servicing it must be replac...

Страница 12: ...uum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit ever 2 500 hours of operation or every three months We also...

Страница 13: ...13 Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Room Heaters This page intentionally left blank...

Страница 14: ...regulator 6 Turn Control knob to pilot position When ignitor button is pressed in there is a spark at the ODS pilot but no ignition 1 Control knob not fully pressed in 2 Control knob not pressed in lo...

Страница 15: ...ee Figure 4 page 7 4 Clean burner orifice see Cleaning and Maintenance on pages 11 and 12 or replace burner orifice White powder residue forming within burner box or on adjacent walls or furni ture 1...

Страница 16: ...eaters IR20LPT IR30LPT BF20LPT BF30LPT 7 2 36 39 38 35 16 21 16 1 16 2 6 26 29 24 22 3 13 23 18 3 11 1 2 1 4 22 2 33 1 22 1 25 9 5 1 3 1 1 27 1 28 1 4 44 42 45 8 20 10 15 14 42 9 7 26 22 3 22 1 33 1 1...

Страница 17: ...Thermostat Valve assembly 1 9 70641 70641 70641 70641 Ignitor Module Mounting Bracket 1 10 70682 70682 70682 70682 High Limit Switch 1 11 70644 70644 70644 70644 Ignitor Module Battery powered 1 12 70...

Страница 18: ...in Relief Grommet 1 70689 70692 Right Burner Gas Tube 1 70690 70693 Right Middle Gas Burner Tube 1 70598 Left Middle Gas Burner Tube 1 70691 70694 Left Burner Gas Tube 1 70695 70695 70696 70696 ODS Ga...

Страница 19: ...19 Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Room Heaters This page intentionally left blank...

Страница 20: ...ctory FOR INFORMATION REGARDING SERVICE Please call Toll Free 800 251 0001 www mrheater com Our office hours are 8 30 AM 5 00 PM EST Monday through Friday Please include the model number date of purch...

Отзывы: