Operating Instructions and Owner’s Manual

                       | Gas-Fired Low-Intensity Infrared Heater

CAUTION

 Label all wires prior to disconnection when

servicing controls. wiring errors can cause improper and
dangerous operation. Verify proper operation after servicing.

The appliance, when installed, must be electrically grounded in
accordance with local code, or in the absence of local codes, with
the

National Electrical Code (ANSI/NFPA 70) or Canadian Electrical

Code (CSA 22.1)

, if an external electrical source is utilized.

Gas Service Installation

Install Gas Supply Lines

A ½” gas supply connection is required as shown below. To check
system pressure, a plugged 1/8” NPT tapping is required upstream
of the manual gas shut-off valve supplied with the heater.

Before connecting the heater to the supply system, verify that all
high pressure testing of the gas piping has been completed.

DO NOT HIGH PRESSURE TEST THE GAS PIPING WITH THE
BURNER CONNECTED.

Follow these instructions to ensure a safe gas supply system
installation:
1. Support all gas piping with suitable pipe hanging materials.

2. Use wrought iron or wrought steel pipe and malleable iron

fittings. The use of copper tube and brass fittings is acceptable

WARNING Electrical Shock Hazard

Plug heater into grounded three prong ceiling receptacle.
Do not cut or remove the grounding prong from this plug.
Do not use with an extension cord.  Failure to follow these
instructions will result in death or electrical shock.

ATTENTION Risque d’électrocution

Brancher le cordon du radiateur sur un socle à 3 broches
et à la masse, situé au plafond. Ne pas sectionner ou
retirer la broche de masse de cette prise. N’utilliser aucun
cable de rallonge. Le non-respect de ces consignes peut
entrainer mort ou electrocution.

Grounding

The heater must be electrically grounded in accordance with the
following codes: United States: Refer to National Electrical Code,
ANSI/NFPA-70 – latest revision. Wiring must conform to the most
current National Electrical Code and local ordinances. Canada: Refer
to Canadian Electrical Code, CSA C22.1 Part 1– latest revision.

Enerco Group, Inc.,  

Low Voltage Thermostat Wiring Diagram

heater

Heaters are normally controlled by thermostat. The 
recommended 24V thermostat, connects to the unit as shown 
in the diagram below.

                  Heater
(maximum 1-per thermostat)

120V-60Hz
Supply Circuit

Low Voltage 
Thermostat
Stock # 10367

Содержание HEATSTAR HST 45

Страница 1: ...service must be performed by a qualified installer service agency or the gas supplier If you cannot reach your gas supplier call the Fire Department Gas Fired Low Intensity Infrared Heaters approved f...

Страница 2: ...e conformer aux precautions et aux instructions a fourni avec cet appareil de chauffage avoir pour resultat la mort blessure et la perte de propriete ou les dommages physiques serieuses du danger de f...

Страница 3: ...er of body oils from the hands to the surface of the reflector VentKit F102840 1 2 3 x 2 Pipe 26GA 2 1 36 x 3 B Vent 3 1 Gas Vent Top 3 4 1 Adj Wall Thimble 5 1 Storm Collar 6 1 3 Elbow 7 1 Adj Roof F...

Страница 4: ...iant energy downward to the space to be heated Heat Exchanger A U shaped tube through which the heated products of combustion pass Rear Movable Hanger Provides support for the heat exchanger and refle...

Страница 5: ...Hz single phase 1 amp Connection 3pinmoldedplug Gas Inlet Connection Connection Male NPT Gas Inlet Pressure The minimum inlet gas supply pressure for the purpose of input adjustment Natural Gas Minimu...

Страница 6: ...HSTtube heater Specifiesthenationalstandardsandapplicablecodes that apply to the gas electric and venting requirements Specifies the national standards and applicable codes that apply to non resident...

Страница 7: ...the floor Minimum required safe distances to combustibles must be maintained from vehicles parked below the heater When installed over hoists the minimum required safe distances to combustible must b...

Страница 8: ...ose Location for Heater When selecting a suitable mounting location for the MHT HSTtube heater it is important to consider the following 1 The heater must meet the minimum mounting height requirement...

Страница 9: ...s when stored under this heater will be subjected to radiant heat and could be seriously damaged 4 All horizontal venting sections must slope away from the heater at a rate of per foot 5 The total len...

Страница 10: ...d through the roof be sure to carefully review the roof option installa tion portion of this section Ensure that the selected mounting site will satisfy the measurement param eters vent length not to...

Страница 11: ...e tube ends extend through the flanges to help with alignment 3 Using the four long and four short nuts from the bolt kit 02876 secure the tube set to the burner box As shown in the diagram use the fo...

Страница 12: ...current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved d...

Страница 13: ...re consistently higher than 40 mph it may be necessary to terminate the vent system above the roof level Other venting references can be found in equipment volume of the ASHRAE Handbook A SINGLE HEATE...

Страница 14: ...approved noncombustible corrosion resistant material as indicated by state and or local codes 2 For horizontal venting the vent lengths may be as follows Minimum Equivalent Length 5 feet of Pipe Maxi...

Страница 15: ...problem the flue length should be shortened or insulated g For vent specifications all of the following conditions must be met The maximum equivalent length of vent pipe should be carefully observed A...

Страница 16: ...Adequate clearances around the perforated fresh air plate must be maintained at all times In larger open areas of buildings infiltration normally is adequate to provide air for combustion DirectOutsid...

Страница 17: ...Use wrought iron or wrought steel pipe and malleable iron fittings The use of copper tube and brass fittings is acceptable WARNING Electrical Shock Hazard Plugheaterinto groundedthreeprongceilingrecep...

Страница 18: ...Use LP resistant joint compound on all threads 4 Check the pipe and tube connections for leaks before placing heating equipment into service When checking for gas leaks use a soap and water solution...

Страница 19: ...ur 8 Periodic visual check of burner flame while unit is in operation through sight glass in bottom of unit Section 6 MAINTENANCE Pre Season Maintenance Heater area to be kept clear and free form comb...

Страница 20: ...iter spark gap incorrect Try This Unplug heater power cord from the electrical outlet wait for a minimum of five seconds Plug heater cord back into outlet Unplug heater power cord from the electrical...

Страница 21: ...equirements contact the gas company Check for 24V across valve terminals Check Shutoff On Valve IF NO Check wiring between the ignition module and the valve Repair replace wires as required If wiring...

Страница 22: ...rs on the illustrations are keyed to the associated parts list E ITEM PART NUMBER DESCRIPTION MHT 45 HST 45 A 02808 Spark Electrode 1 1 B 02837 IgnitionWire 1 1 05795 Orifice NG 05747 Orifice LP D 027...

Страница 23: ...08850 F202851 MHT 45LP BurnerBoxfor F208851 B F106250 MHT HST 45 Tube Set C 06014 Hanger D 06016 Hanger Clamp E 06008 9 MHT HST 45 R eflector F 06009 Reflector End Cap MHT HST45Tube Heater REPLACEMENT...

Страница 24: ...and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There are no other warranties express or implied Specifically there...

Отзывы: