Commissioning
Waterpilot FMX21
68
Hauser
Menu Setup → Level (LEVEL) → ZERO
• RIA15 parameter: ZERO
• Corresponds to device parameter: Pos. zero adjust
• Values (default in bold)
•
NO
• YES
• Visible with: gauge pressure sensor
• Description:
• For performing a position adjustment (gauge pressure sensor).
• The value 0.0 is assigned to the pressure value present. The current value is also
corrected.
Menu Setup → Level (LEVEL) → P_LRV
• RIA15 parameter: P_LRV
• Corresponds to device parameter: Empty pressure
• Values (default in bold)
• -1999.9 to 9999.9
•
Gauge pressure sensor: Sensor LRL
• Absolute pressure sensor: 0
• Description:
Pressure empty calibration using keys -, +, E. More in-depth description / valid value
range: any value in the range indicated
. Number of decimal places depends on the
configured pressure unit.
Menu Setup → Level (LEVEL) → P_URV
• RIA15 parameter: P_URV
• Corresponds to device parameter: Full pressure
• Values (default in bold)
• -1999.9 to 9999.9
•
Sensor URL
• Description:
Pressure full calibration using keys -, +, E. More in-depth description / valid value range:
any value in the range indicated
. Number of decimal places depends on the
configured pressure unit.
Menu Setup → Level (LEVEL) → EMPTY
• RIA15 parameter: EMPTY
• Corresponds to device parameter: Empty calibration
• Values (default in bold)
• -1999.9 to 9999.9
•
0
• Description:
Level empty calibration using keys -, +, E. More in-depth description / valid value range:
any value in the range indicated
Number of decimal places depends on the
configured level unit.
Menu Setup → Level (LEVEL) → FULL
• RIA15 parameter: FULL
• Corresponds to device parameter: Full calibration
• Values (default in bold)
• -1999.9 to 9999.9
•
100
• Description:
Level full calibration using keys -, +, E. More in-depth description / valid value range:
any value in the range indicated
. Number of decimal places depends on the
configured level unit.
5)
The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure" and "Set LRV/Set URV" must be at least 1% apart. The value will be
rejected, and a message displayed, if the values are too close together. Further limit values are not checked, i.e. the values entered must be
appropriate for the sensor module and the measuring task for the device to be able to measure correctly.