![Endress+Hauser Thermophant T TTR 35 Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/endress-hauser/thermophant-t-ttr-35/thermophant-t-ttr-35_operating-instructions-manual_2407418021.webp)
Thermophant T TTR31, TTR35
Operating options
Hauser
21
•
Delay times for switch point SP and switchback point RSP can be configured in
increments of 1 s.
This makes it possible to filter out undesired temperature peaks of short duration or of high
frequency.
•
Factory setting (if no customer-specific setting is ordered)
Switch point SP1: 45 °C (113 °F); switchback point RSP1: 44.5 °C (112.1 °F)
Switch point SP2: 55 °C (131 °F); switchback point RSP2: 54.5 °C (130.1 °F)
•
Range of adjustment
LRL = Lower Range Limit
URL = Upper Range Limit
LRV = Lower Range Value
URV = Upper Range Value
t
t
1
2
3
4
T
A
B
T
SP
SP
RSP
RSP
0
0
0
0
1
1
1
1
A0023240
9
Switch point functions
A
Hysteresis function
B
Window function
1
Window - NC contact
2
Hysteresis - NC contact
3
Window - NO contact
4
Hysteresis - NO contact
SP Switch point
RSP Switchback point