Operation
TTR31, TTR35
16
Hauser
5.1.4
Basic settings
!
Note!
The function group 4-20 is only available if the 4 to 20 mA analog output (
0>.,
) is selected in
the function group
or
.
under
6
or
6.
.
Function
group
Function
Settings
Description
Technical unit
C
C6
Select technical unit:
°C, °F, K
Factory setting:
°C
Configure zero
point
,M,
Position adjustment:
within ±10 °C/K
(±18 °F) of the upper
range limit
7 @
Accept zero point
,M,
No settings possible (not
available in PC software)
Display
66
66
PV: measured value
display
PVRO: measured value
display rotated 180°
SP: set switch point
display
SPRO: set switch point
display rotated 180°
OFF: display off
OFFR: display off rotated
180°
Factory setting:
measured value (PV)
Damping:
display value,
output signal
,M,
Measured value damping
with regard to display
value and output: 0 (no
damping) or 9 to 40 s (in
increments of 1 second)
Factory setting:
0 s