TTR31, TTR35
Wiring
Hauser
11
4
Wiring
!
Note!
TTR35: Electrical cables must comply with 3-A standard. They must be smooth, corrosion
resistant and cleanable.
4.1 DC voltage version with M12x1 connector
P01-PTx3xxxx-04-xx-xx-xx-002
Fig. 7: Thermophant
®
T with M12x1 connector
A1: 1x PNP switch output
A2: 2x PNP switch outputs R1 and
m
(R2)
A2’: 2x PNP switch outputs R1 and
m
(diagnosis/break contact with adjustment "DESINA")
A3: 1x PNP switch output and 1x analog output (4 to 20 mA)
A4: 1x analog output (4 to 20 mA) and 1x PNP switch output
m
(R2)
A4’: 1x analog output (4 to 20 mA) and 1x PNP switch output
m
(diagnosis/break contact with adjustment "DESINA")
"
Caution!
To avoid the analog input damaging of a PLC, do not connect the active PNP switch output of
the device to the 4...20 mA input of a PLC.
!
Note!
More informations about DESINA see www.desina.de (
→
Chap. 5.1.4 Basic settings).