Hauser
31
Fault
Reason
Remedy
Does not switch
No power
Check power
Faulty signal line
Check signal line
Faulty electronic insert
Exchange
Density of bulk solids too low
Set density to >200 g/l at
electronic insert; see page 19
Rod encrusted
Clean rod
FEM24:
Contacts welded together
(after short-circuit)
Exchange FEM24;
put fuse in contact circuit
Switches incorrectly
Min-/Max-fail-safe mode set wrongly
Set correct mode at electronic insert
Sporadic
faulty switching
Extreme RFI
Use screened cable
Extreme vibration
Decouple sensor mechanically,
turn oscillating rod 90°
Water in housing
Drain;
Screw cover and cable bushings tight
FEM22:
Output overloaded
Reduce load, (cable) capacitance