Commissioning
Solicap M FTI55, FTI56
74
Hauser
6.4.5
MIN/MAX failsafe mode
!
Note!
By selecting the failsafe mode correctly, you ensure that the output always operates safely with
quiescent current.
–
Minimum failsafe mode (MIN)
: The output switches if the switch point is undershot (rod/rope
uncovered), a fault occurs or the line voltage fails.
–
Maximum failsafe mode (MAX)
: The output switches if the switch point is exceeded (rod/
rope covered), a fault occurs or the line voltage fails.
6.4.6
Display calibration situation
You can use this function to see what calibrations have been performed on the device. The
calibration situation is indicated by the three LEDs.
To query the calibration situation, proceed as follows:
1.
Press the
B
key for at least 2 s.
2.
The current calibration situation is indicated by the LEDs (operating/switching status).
6.4.7
Displaying the diagnostic code
This function makes it possible to interpret faults using the three LEDs. If the system detects more
than one fault, the fault with the highest priority is shown on the display.
Further information is provided in the "Fault diagnostics" section
ä
79.
DIP
switch: F
Function
G
Failsafe mode: MIN
The output switches safety-oriented when the probe is uncovered (signal on
alarm). For use for dry running protection and pump protection for example
G
Failsafe mode: MAX
The output switches safety-oriented when the probe is covered (signal on
alarm). For use with overfill protection for example
Light emitting diodes (LED signals)
Calibration situation
Green
LED 1
Operational
Red
LED 2
Fault
Yellow LED 3
Switching
status
No calibration
On
Empty calibration performed
On
Full calibration performed
On
On
Empty and full calibration performed
MAX
MIN
MAX