7.1
Relay settings
Relay assignment
In V1H4 and V1H9, relays 1 or 2 can be assigned to the corresponding measuring
channel by entering the channel number »1« or »2«.
Step
Matrix Entry Significance
1
V1H9
e.g. 1
Relay 2 is assigned to channel 1
2
-
»E«
Register entry
Switch point
The switch point is set at V1H0 for relay 1 and V1H5 for relay 2 in the units used for
calibration or linearization.
Step
Matrix Entry Significance
1
V1H0
e.g. 200
Switch point for relay 1 (in the unit displayed in field V0H0)
2
-
»E«
Registers entry
Note!
•
If the relays are assigned to channel 2, the switch point is set at V8H6 as described
in Chapter 8, Section 8.2 and 8.3.
Fail-safe mode
This function determines whether the relay is to act as a minimum or maximum limit
switch, entries are made at V1H1 for relay 1 and V1H6 for relay 2:
•
0 = minimum fail-safe: the relay de-energises if the level or volume drops
below the value
•
1 = maximum fail-safe: the relay de-energises if the level or volume rises
above the value
Step
Matrix Entry
Significance
1
V1H1
e.g. 0
Relay 1 de-energises when the product level drops below
the switch point
2
-
»E«
Register entry
Minimum fail-safe mode, setting 0
Maximum fail-safe mode, setting 1
Level
Relay status
LED
Level
Relay status
LED
Drops below
switch point
De-energised
Green off
Red on
Rises above
switch point
De-energised
Green off
Red on
Rises above
switch point
Energised
Green on
Red off
Drops below
switch point
Energised
Green on
Red off
Table 7.2:
Function of the relays at
minimum and maximum
fail-safe mode
z18 d20 z20
z22 d24 z24
z18 d20 z20
z22 d24 z24
z18 d20 z20
z22 d24 z24
z18 d20 z20
z22 d24 z24
Silometer FMC 671 Z/676 Z
Chapter 7: Limit Switches
37