Outputs
Number
1
Open circuit
voltage
24 V ± 10%
Over range
10%
Load
(impedance)
0...700
Ω
(without communication resistance)
Galv. isolation
To all other current circuits
Power supply
Electrical connection
Power supply
20...253 V DC/AC, 50/60 Hz
Power
consumption
Max. 2.4 W
Current
requirement
(input current limitation)
I
max
/ I
n
< 15
Electrical
Safety
To EN 61 010-1, Protection class I, Over voltage category II,
Over current protection at installation (fuse)
≤
10 A
20...253 V
DC/AC
50/60 Hz
HART
®
connection
sockets
Output with
loop power supply
Input
(option intrinsically safe)
Active barrier
22