Device configuration
Description of operating functions
The following table shows the menus available for the field indicator. These are explained in detail
in the sections specified.
7.1
Data processing (INPUT)
7.1.1
Input range
INPUT
É
CURVE
É
Options: Linear (LINAR) or square root (SQRT).
The input range is a 4 - 20 mA signal.
Select the type of input signal here (linear or quadratic).
7.1.2
Damping
INPUT
É
DAMP
É
Options: 0 - 99 (0 = no damping)
• Measured value damping can be set between 0 and 99 s.
• Only whole numbers can be entered.
• The factory setting is 0 (no damping).
7.1.3
Measured value scaling
Section
Function
As shown on the display
Data processing
INPUT
Display
DISPL
Limit values
LIMIT
Other settings
PARAM
Service level
SERV
Name
Description
Measured value decimal point
'DI DP'
Indicates the number of places after the decimal point for the numerical display of the
measuring range.
– Selection range 0 - 3 places after decimal point
– Default: 1 place after decimal point
If the number of spaces after the decimal point is increased, the value for all the
dependent operating parameters must be recalculated based on the formula new value
= old value * 10
PDnew - PDold
. If the value of one of the dependent operating parameters
is < -19999 or > 99999, the number of places after the decimal point cannot be
increased and error message C561 is shown on the display.
Measured value 0 % 'DI LO'
Indicates the display value for the 4 mA value.
– Value range -19999 to 99999
– Default: 0.0
Measured value 100 % 'DI HI'
Indicates the display value for the 20 mA value.
– Value range -19999 to 99999
– Default: 100.0
Measured value offset 'OFFST'
This is used to correct the display measured value. The offset is added to the measured
value.
– Value range -19999 to 99999
– Default: 0.0