Prosonic T
Mounting
Hauser
9
Example: Triangular weir
L00-FMU30xxx-17-00-00-xx-012
BD Blocking distance
E
Empty calibration
F
Full calibration
2.4
Measuring range
2.4.1
Blocking distance, Nozzle mounting
Install the instrument at a height so that the blocking distance BD is not undershot, even at
maximum fill level. Use a pipe nozzle if you cannot maintain the blocking distance in any other
way. The interior of the nozzle must be smooth and may not contain any edges or welded joints.
In particular, there should be no burr on the inside of the tank side nozzle end. Note the
specified limits for nozzle diameter and length. To minimise disturbing factors, we recommend
an angled socket edge (ideally 45°).
min. 3 H
H
min. 2 H
a
min. 2 H
BD
max
max
max
max
E
(= F)
Содержание Prosonic T FMU30
Страница 29: ...Prosonic T Commissioning Endress Hauser 29...
Страница 30: ...Commissioning Prosonic T 30 Endress Hauser...
Страница 31: ...Prosonic T Commissioning Endress Hauser 31...
Страница 32: ...KA01054F 00 EN 13 11 71145341 CCS FM SGML 9 0 71145341...