Commissioning

Prosonic T

26

Hauser

5.3.3

Empty and full calibration

Function 

Remarks

"empty calibr." (005)

This function is used to enter the distance from the sensor membrane (reference point of 
the measurement) to the minimum level (=zero).

"

Caution! 

With dished boiler heads or conical outflows, the zero point should not be deeper than the 
point at which the ultrasonic wave impinges on the tank bottom.

L00-FMU30-15-00-00-xx-001

BD Blocking distance

F

Full calibration (= span)

SD Safety distance

D

Nozzle diameter

E

Empty calibration (= zero point)

L

Level

"blocking distance" (059)"  In this function the blocking distance (BD) of the sensor is displayed.

"

Caution! 

When entering the full calibration (span), please take into account, that the maximum level 
may not project into the blocking distance (BD).

!

Note! 

After basic calibration, enter a safety distance (SD) in the 

"safety distance" (015)

 

function. If the level is within this safety distance, the device signals a warning or an alarm, 
depending on your selection in the 

"in safety distance" (016)

 function.

"full calibr." (006)

This function is used to enter the distance from the minimum level to the maximum level 
(=span).

20 mA

100%

4 mA

0%

D

L

E

F

BD

SD

Содержание Prosonic T FMU30

Страница 1: ...l Measurement These Instructions are Brief Operating Instructions they do not replace the Operating Instructions included in the scope of supply For detailed information refer to the Operating Instruc...

Страница 2: ...e storage 4 2 2 Installation 5 2 3 Installation conditions 6 2 4 Measuring range 9 2 5 Installation hint 12 2 6 Installation check 12 3 Wiring 13 3 1 Wiring 13 3 2 Terminal assignment 14 3 3 Supply vo...

Страница 3: ...ly permitted in the Operating Instructions see CD ROM If faults cannot be rectified the device must be taken out of service and secured against unintentional commissioning Do not operate damaged devic...

Страница 4: ...al provides the optimum protection for this The permissible storage temperature is 40 C to 80 C 40 F to 176 F Symbol Meaning Warning A warning highlights actions or procedures which if not performed c...

Страница 5: ...002 A Installation with counter nut 1 Counter nut PC supplied for G1 and G2 instruments B Installation with sleeve 1 Sealing ring EPDM supplied C Installation with installation bracket D Installation...

Страница 6: ...ided Avoid measurements through the filling curtain 4 For solid application where bulk solid cones appear align the sensor membrane perpendicular to the surface Make sure that equipment 5 such as limi...

Страница 7: ...nstrument in the middle of the channel or weir Align the sensor membrane parallel to the water surface Keep to the installation distance of the channel or weir In narrow shafts with strong interferenc...

Страница 8: ...ndress Hauser Example Khafagi Venturi flume L00 FMU30xxx 17 00 00 xx 003 A Khafagi Venturi flume B Inflow C Outflow BD Blocking distance E Empty calibration F Full calibration V Direction of flow 1 x...

Страница 9: ...is not undershot even at maximum fill level Use a pipe nozzle if you cannot maintain the blocking distance in any other way The interior of the nozzle must be smooth and may not contain any edges or w...

Страница 10: ...D Maximum nozzle length mm in Nozzle diameter 1 sensor 2 sensor DN50 2 80 3 15 DN80 3 240 9 45 240 9 45 DN100 4 300 11 8 300 11 8 DN150 6 400 15 7 400 15 7 DN200 8 400 15 7 400 15 7 DN250 10 400 15 7...

Страница 11: ...r message The output signal assumes the value defined in the Output on alarm 011 function MAX MIN user specific value or holds the last value As soon as the level drops below the safety distance the d...

Страница 12: ...e device damaged visual inspection Does the device correspond to the measuring point specifications for process temperature process pressure ambient temperature measuring range etc If available Are th...

Страница 13: ...standards and the specifications in the safety instructions XA s Make sure you use the specified cable gland 3 1 Wiring 1 Unscrew housing cover 1 2 Remove display 2 if fitted 3 Insert cable 3 through...

Страница 14: ...x 04 00 00 de 015 1 Power 2 Plant ground 3 4 20 mA 3 3 Supply voltage The following values are the voltages across the terminals directly at the instrument L L 1 2 3 1 2 3 Current consumption Terminal...

Страница 15: ...the tank by the plastic sensor interference signals may occur if the potential matchin gline is not prolerly connected For optimum electromagnetic compatibility the potential matching line should be a...

Страница 16: ...nsists of one or more functions The functions perform the actual operation or parameterisation of the instrument Numerical values can be entered here and parameters can be selected and saved The avail...

Страница 17: ...lay and operating elements On site display VU331 The LCD module for display and operation is located beneath the housing cover The measured value is legible through the transparent cover Open the cove...

Страница 18: ...segmented in 10 bars Each completely filled bar represents a change of 10 of the adjusted span measured value display 1 label 2 symbol 3 value 4 bargraph 5 unit 6 position in menu group selection 1 s...

Страница 19: ...e if no input is possible Key s Meaning The keys to press are displayed in grey Navigate upwards in the selection list Edit numeric value within a function Navigate downwards in the selection list Ed...

Страница 20: ...ct the language this message appears the first time the instrument is switched on 2 distance unit Select the basic unit this message appears the first time the instrument is switched on 3 measured val...

Страница 21: ...Setup 5 3 1 Overview basic setup L00 FMxxxxxx 19 00 00 en 001 tank shape dome ceiling medium property Unknown process cond Standard safety settings linearisation extended calibr empty calibr full cali...

Страница 22: ...nce echo suppression tank mapping Details Chap 5 3 4 7 dist measured value 008 The distance measured from the reference point to the product surface and the meas value calculated with the aid of the e...

Страница 23: ...FMU30KAx 14 00 06 xx 001 medium property 003 Set the medium type in this function You have the following options unknown e g pasty media such as greases creams gels etc liquid solid grain size 4 mm fi...

Страница 24: ...ime turbulent surface Storage accumulation tanks with uneven surface due to free filling mixing nozzles or small bottom stirrers L00 FMU30xxx 14 00 00 xx 002 Special filters for stabilizing the input...

Страница 25: ...ty bulk solids L00 FMU30xxx 14 00 00 xx 007 The averaging filters are set to detect even relatively weak signals conveyor belt Bulk solids with rapid level change L00 FMU30xxx 14 00 00 xx 005 The aver...

Страница 26: ...distance D Nozzle diameter E Empty calibration zero point L Level blocking distance 059 In this function the blocking distance BD of the sensor is displayed Caution When entering the full calibration...

Страница 27: ...xx 14 00 06 xx 010 1 Distance too small 2 Distance ok Select distance ok if the correct distance is displayed Any echoes closer to the sensor will be suppressed by the following interference echo supp...

Страница 28: ...rrect basic setup completed Distance incorrect level incorrect a further interference echo mapping must be carried out checkdistance 051 Distance correct level incorrect check emptycalibr 005 Return t...

Страница 29: ...Prosonic T Commissioning Endress Hauser 29...

Страница 30: ...Commissioning Prosonic T 30 Endress Hauser...

Страница 31: ...Prosonic T Commissioning Endress Hauser 31...

Страница 32: ...KA01054F 00 EN 13 11 71145341 CCS FM SGML 9 0 71145341...

Отзывы: