Prosonic Flow 92
11 Description of device functions
Hauser
85
Unit (Output)
Use this function to assign a measured value and its unit to the current out-
put.
Metric options volume flow:
L/s – L/min – L/h – ML/d – m3/s – m3/min – m3/h – Mm3/d – BBL/s – BBL/min
– BBL/h – MBBL/d
US options volume flow:
gal/s – gal/min – gal/h – Mgal/d – ft3/s – ft3/min – ft3/h – Mft3/d – BBL/s –
BBL/min – BBL/h – MBBL/d
Options flow velocity:
m/s (metric) – ft/s (US)
Factory setting:
m/s
Note!
This setting influences the function “OUTPUT RANGE” (see next page).
Output Range
Use this function to define the maximum range of a measured value (i.e.
maximum range for volume flow or flow velocity) which can be output via the
current output. The specified range of 0...“Output Range” (maximum value
for the measurement variable) is converted to a current output between
4...20 mA.
Note!
• Unit and definition of the measured value depend on the selection in
function “UNIT” (see Page 85).
• The current output function can be disabled by setting the output range to
“0.000E0”.
Factory setting:
4.000E0
Inputs and Outputs