Proline Prowirl 73
Commissioning
Hauser
25
5.4
Calling the Commissioning Quick Setup
!
Note!
The procedure described here only applies to measuring devices with HART communication.
Measuring devices with PROFIBUS PA and FOUNDATION Fieldbus communication do not
have a Commissioning Quick Setup.
All the functions needed for commissioning are called up automatically with the Quick Setup.
The functions can be changed and adapted to the process in question.
1.
F
Enter the function matrix (starting with measured value display)
2.
P
Select the group QUICK SETUP
F
Confirm selection
3.
QUICK SETUP COMMISSIONING function appears.
4.
Intermediate step if configuration is blocked:
P
Enter the code
73
(confirm with
F
) and thus enable configuration
5.
P
Go to Commissioning Quick Setup
6.
P
Select YES
F
Confirm selection
7.
F
Start Commissioning Quick Setup
8.
Configure the individual functions/settings:
– Via
P
-key, select option or enter number
– Via
F
-key, confirm entry and go to next function
– Via
Q
-key, return to Setup Commissioning function
(settings already made are retained)
All the available functions of the measuring device and their configuration options as well as
additional Quick Setups, if available, are described in detail in the Operating Instructions. The
related Operating Instructions can be found on the CD-ROM.
The measuring device is ready for operation on completion of the Quick Setup.