Proline Promass O 300
Hauser
31
Electrical connection
Connecting the transmitter
• Terminal assignment→ 26
• Device plugs available→ 27
1
2
3
4
A0026781
1
Terminal connection for supply voltage
2
Terminal connection for signal transmission, input/output
3
Terminal connection for signal transmission, input/output or terminal for network connection via service
interface (CDI-RJ45); Optional: terminal connection for external WLAN antenna or connection for remote
display and operating module DKX001
4
Protective ground (PE)
An adapter for RJ45 and the M12 connector is optionally available:
Order code for "Accessories", option
NB
: "Adapter RJ45 M12 (service interface)"
The adapter connects the service interface (CDI-RJ45) to an M12 connector mounted in the
cable entry. Therefore the connection to the service interface can be established via an M12
connector without opening the device.
Network connection via service interface (CDI-RJ45) → 79
Connecting in a ring topology
Device versions with EtherNet/IP and PROFINET communication protocols can be integrated into a
ring topology. The device is integrated via the terminal connection for signal transmission (output 1)
and the connection to the service interface (CDI-RJ45).
Integrate the transmitter into a ring topology:
• EtherNet/IP → 77
• PROFINET → 78
1
2
3
4
A0026781
1
Terminal connection for supply voltage
2
Terminal connection for signal transmission: PROFINET or EtherNet/IP (RJ45 connector)
3
Connection to service interface (CDI-RJ45)
4
Protective earth (PE)
If the device has additional input/outputs, these are routed via the cable entry for the
connection to the service interface (CDI-RJ45).