Technical data
Proline Promass O 100 HART
96
Hauser
max(G)
<
max(F)
max(G)
can never be greater than
max(F)
ρ
G
Gas density in [kg/m³] at operating conditions
DN
x
[mm]
[in]
[kg/m
3
]
80
3
155
100
4
130
150
6
200
Calculation example for gas
• Sensor: Promass O, DN 80
• Gas: Air with a density of 60.3 kg/m³ (at 20 °C and 50 bar)
• Measuring range (liquid):180
000 kg/h
• x = 130 kg/m³ (for Promass O, DN 80)
Maximum possible full scale value:
max(G)
=
max(F)
· ρ
G
: x = 180
000 kg/h · 60.3 kg/m³ : 130 kg/m³ = 83
500 kg/h
Recommended measuring range
"Flow limit" section (→ 105)
Operable flow range
Over 1000 : 1.
Flow rates above the preset full scale value are not overridden by the electronics unit, with
the result that the totalizer values are registered correctly.
16.4 Output
Output signal
Current output
Current output
4-20 mA HART (active)
Maximum output values
• DC 24 V (no flow)
• 22.5 mA
Load
0 to 700 Ω
Resolution
0.38 µA
Damping
Adjustable: 0.07 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
The range of options increases if the measuring device has one or more
application packages.
Pulse/frequency/switch output
Function
Can be set to pulse, frequency or switch output
Version
Passive, open collector
Содержание Proline Promass O 100HART