Proline Promass F 200 HART
Commissioning
Hauser
85
Simulation current
output 1-2
-
Switch simulation of
the current output
on and off.
• Off
• On
Off
Value current
output 1-2
The
On
option is selected in the
Simulation current output
1-2
parameter.
Enter the current
value for simulation.
3.6 to 22.5 mA
Current value
currently measured
Frequency
simulation
-
Switch simulation of
the frequency
output on and off.
• Off
• On
Off
Frequency value
The
On
option is selected in the
Frequency output
simulation
parameter.
Enter the frequency
value for simulation.
0 to 1
250 Hz
Frequency currently
measured
Pulse simulation
-
Set and switch off
pulse output
simulation.
• Off
• Fixed value
• Down-count val.
If the
Fixed
value
option
is selected,
the
Pulse
width
parameter
defines the
pulse width of
the pulses
output
(
Off
Pulse value
The
Down-count. val.
option
is selected in the
Simulation
pulse output
parameter.
Enter the number of
pulses for
simulation.
0...65535
Pulse currently
measured
Switch output
simulation
-
Switch simulation of
the switch output on
and off.
• Off
• On
Off
Switch status
The
On
option is selected in the
Switch output simulation
parameter.
Select the status of
the status output for
the simulation.
• Open
• Closed
Open
Simulation device
alarm
-
Switch the device
alarm on and off.
• Off
• On
Off
10.8
Protecting settings from unauthorized access
The following options exist for protecting the configuration of the measuring device from
unintentional modification after commissioning:
• Write protection via access code (
• Write protection via write protection switch (
• Write protection via keypad lock (
10.8.1 Write protection via access code
With the customer-specific access code, the parameters for the measuring device configuration are
write-protected and their values can no longer be changed via local operation.