Commissioning
Proline Cubemass C 300
100
Hauser
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Assign limit
The
Limit
option is selected in
the
Relay output function
parameter.
Select process variable for limit
function.
• Mass flow
• Volume flow
• Corrected volume
flow
• Target mass flow
• Carrier mass flow
• Target volume
flow
• Carrier volume
flow
• Target corrected
volume flow
• Carrier corrected
volume flow
• Density
• Reference density
• Concentration
• Temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Oscillation
damping
• Pressure
• Application
specific output 0
• Application
specific output 1
• Inhomogeneous
medium index
• Suspended bubbles
index
Mass flow
Assign diagnostic behavior
In the
Relay output function
parameter, the
Diagnostic
behavior
option is selected.
Select diagnostic behavior for
switch output.
• Alarm
• Alarm or warning
• Warning
Alarm
Assign status
In the
Relay output function
parameter, the
Digital Output
option is selected.
Select device status for switch
output.
• Partially filled pipe
detection
• Low flow cut off
Partially filled pipe
detection
Switch-off value
In the
Relay output function
parameter, the
Limit
option is
selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
• 0 kg/h
• 0 lb/min
Switch-off delay
In the
Relay output function
parameter, the
Limit
option is
selected.
Define delay for the switch-off
of status output.
0.0 to 100.0 s
0.0 s
Switch-on value
The
Limit
option is selected in
the
Relay output function
parameter.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
• 0 kg/h
• 0 lb/min
Switch-on delay
In the
Relay output function
parameter, the
Limit
option is
selected.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
0.0 s
Failure mode
–
Define output behavior in
alarm condition.
• Actual status
• Open
• Closed
Open
*
Visibility depends on order options or device settings
10.4.10 Configuring the double pulse output
The
Double pulse output
submenu guides the user systematically through all the
parameters that have to be set for configuring the double pulse output.