Commissioning
Levelflex FMP50 PROFIBUS PA
26
Hauser
7.
Setup → Empty calibration
Specify the empty distance E (distance from the reference point R to the 0% mark).
8.
Setup → Full calibration
Specify the full distance F (distance from the 0% mark to the 100% mark).
9.
Setup → Level
Displays the measured level L (for verification purposes).
10.
Setup → Distance
Displays the distance D between the reference point R and the level L (for
verification purposes).
11.
Setup → Signal quality
Displays the signal quality of the analyzed level echo (for verification purposes).
12.
Setup → Mapping → Confirm distance
Compare the distance displayed with the actual value to start recording an
interference echo map.