Levelflex FMP50 PROFIBUS PA
Commissioning
Hauser
25
8.3
Device configuration
8.3.1
Configuring level measurement
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
A0011360
10
Configuration parameters for level measurement in liquids
LN = Probe length
R = Reference point of measurement
D = Distance
E = Empty calibration (= zero point)
L = Level
F = Full calibration (= span)
1.
Setup → Device tag
Enter device tag.
2.
Setup→ Device address
Enter the device bus address (only if the address is set via the software).
3.
Setup → Distance unit
Select the length unit.
4.
Setup → Tank type
Select tank type.
5.
Setup → Tube diameter
(only for "Tank type" = "Bypass / pipe")
Specify the diameter of the bypass or stilling well.
6.
Setup → Medium group
Specify the medium group (
Others
or
Water based (DC >= 4)
)