Commissioning
Micropilot S FMR540 4 to 20 mA HART
52
Hauser
Function "set value" (009)
This function enables the user to offset the difference between the reference level and the measured
level (or between ullage value and measured distance). To make an offset effective, input the
reference level measured by the dip measurement by using key buttons. The software offsets the
dist./meas value with the difference between reference level and measured value.
L00-FMR540xx-19-00-00-en-007
!
Note!
After the basic setup, an evaluation of the measurement with the aid of the envelope curve
(function group
"Envelope curve" (0E)
) is recommended.
⇒
E HAUSER
E
+
–
Empty
Value
Level
(measured)
Level
(reference)
Ullage
(measured)
Liquid surface
Dipping
UIlage
Level
UIlage
(reference)
datum plate
Level (Reference) is the value to be input in "
"
Function.
set value (009)
⇒
⇓
After 3 s, the following message appears
E HAUSER
E
+
–