Micropilot M
12
Hauser
Performance characteristics
Reference operating
conditions
•
temperature = +20 °C (68 °F) ±5 °C (9 °F)
•
pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi)
•
relative humidity (air) = 65 % ±20%
•
ideal reflector
•
no major interference reflections inside the signal beam
Maximum measured error
Typical statements for reference conditions, include linearity, repeatability, and hysteresis:
.
Resolution
Digital / analog in % 4…20 mA
•
FMR 230: 1mm / 0.1 % of measuring range
•
FMR 231: 1mm / 0.1 % of measuring range
•
FMR 240: 1mm / 0.1 % of measuring range
Reaction time
The reaction time depends on the parameter settings (min. 1 s). In case of fast level changes, the
instrument needs the reaction time to indicate the new value.
Influence of ambiente
temperature
0.006% / 10 K referring to max. measuring range
Type of device
to 10 m
ex 10 m
FMR 230
±10 mm
±0.1% of measuring range
FMR 231
±10 mm
±0.1% of measuring range
FMR 240
±3 mm
±0.03% of measuring range