Operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
132
Hauser
•
Distance too small
To be selected if the measured distance is smaller than the actual distance. The device
searches for the next echo and returns to the
Confirm distance
parameter. The distance
is recalculated and displayed. The comparison must be repeated until the displayed
distance matches the actual distance. After this, the recording of the map can be started
by selecting
Distance ok
.
•
Distance too big
To be selected if the measured distance exceeds the actual distance. The device adjusts
the signal evaluation and returns to the
Confirm distance
parameter. The distance is
recalculated and displayed. The comparison must be repeated until the displayed
distance matches the actual distance. After this, the recording of the map can be started
by selecting
Distance ok
.
•
Tank empty
To be selected if the tank is completely empty. The device records a mapping covering
the complete measuring range as defined by the
Tank/silo height
parameter
Tank/silo height
=
Empty calibration
.
Take into account that in case of conical outlets, for example, a measurement is only
possible up to the point at which the radar hits the bottom of the tank or silo. If the
Tank empty
option is used,
Tank/silo height
may
not reach below this point as otherwise the empty signal is suppressed.
•
Factory map
To be selected if the present mapping curve (if one exists) is to be deleted. The device
returns to the
Confirm distance
parameter and a new mapping can be recorded.
When operating via the display module, the measured distance is displayed together
with this parameter for reference purposes.
If the teaching procedure with the
Distance too small
option or the
Distance too big
option is quit before the distance has been confirmed, a map is
not
recorded and the
teaching procedure is reset after 60 s.
Present mapping
Navigation
Setup → Present mapping
Description
Indicates up to which distance a mapping has already been recorded.
Mapping end point
Navigation
Setup → Map. end point
Prerequisite
Manual map
or
Distance too small
Description
Specify new end of the mapping.
User entry
0.1 to 999
999.9 m
Factory setting
0.1 m
5)
Only available for "Expert → Sensor → Echo tracking →
Evaluation mode
parameter" = "Short time history" or "Long time history"
Содержание Micropilot FMR56