Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Operating menu
Hauser
131
Signal quality
Navigation
Setup → Signal quality
Description
Displays the signal quality of the level echo.
Additional information
Meaning of the display options
•
Strong
The evaluated echo exceeds the threshold by at least 10 dB.
•
Medium
The evaluated echo exceeds the threshold by at least 5 dB.
•
Weak
The evaluated echo exceeds the threshold by less than 5 dB.
•
No signal
The device does not find a usable echo.
The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level echo or the tank bottome echo. To differentiate between these two,
the quality of the tank bottom echo echo is always displayed in brackets.
In case of a lost echo (
Signal quality = No signal
) the device generates the following
error message:
• F941, for
Output echo lost (→ 153) = Alarm
.
• S941, if another option has been selected in
.
Confirm distance
Navigation
Setup → Confirm distance
Description
Specify, whether the measured distance matches the real distance.
Depending on the selection the device automatically sets the range of mapping.
Selection
• Manual map
• Distance ok
• Distance unknown
• Distance too small
• Distance too big
• Tank empty
• Factory map
Factory setting
Distance unknown
Additional information
Meaning of the options
•
Manual map
To be selected if the range of mapping is to be defined manually in the
Mapping end
point
parameter (→ 132). In this case it is not necessary to confirm the distance.
•
Distance ok
To be selected if the measured distance matches the actual distance. The device
performs a mapping.
•
Distance unknown
To be selected if the actual distance is unknown. A mapping can not be performed in this
case.
*
Visibility depends on order options or device settings
Содержание Micropilot FMR56
Страница 197: ......
Страница 198: ...www addresses endress com 71344036 71344036 ...