Micropilot FMR53, FMR54
Hauser
V. 1, Rev. 7, 26-10-2012
15
Permanent entries
1
Client VCRs
0
Server VCRs
10
Source VCRs
43
Sink VCRs
0
Subscriber VCRs
43
Publisher VCRs
43
Device Link Capabilities
Slot time
4
Min. inter PDU delay
8
Max. response delay
20
Transducer Blocks
Block
Content
Output values
Setup Transducer Block
Contains all parameters for a standard commissioning
procedure
• Level or volume
1)
(Channel 1)
• Distance (Channel 2)
Advanced Setup Transducer
Block
Contains all parameters for a more detailed configuration
of the device
no output values
Display Transducer Block
Contains all parameters for the configuration of the
display module
no output values
Diagnostic Transducer Block
Contains diagnostic information
no output values
Expert Configuration
Transducer Block
Contains parameters which require detailed knowledge
of the functionalities of the device
no output values
Expert Information
Transducer Block
Contains information about the state of the device
no output values
Service Sensor Transducer
Block
Contains parameters which can only be operated by
Hauser service personnel
no output values
Service Information
Transducer Block
Contains information on the state of device which is
relevant for service operations
no output values
Data Transfer Transducer
Block
Contains parameters which allow to backup the device
configuration in the display module and to restore it into
the device.
no output values
1)
depending on the configuration of the block
Function Blocks
Block
Content
Number of
permanent
blocks
Number of
instantiable
blocks
Execution
time
Functionality
Resource Block The Resource Block contains all the data
that uniquely identifies the field device.
It is an electronic version of a nameplate
of the device.
1
0
-
enhanced
Multiple
Analog Input
Block
The AI block takes the manufacturer's
input data, selected by channel number,
and makes it available to other function
blocks at its output.
2
3
25 ms
enhanced
Discrete Input
Block
The DI block takes a discrete input value
(e.g. indication of an level limit), and
makes it available to other function
blocks at its output.
1
2
20 ms
standard