Micropilot FMR51, FMR52 HART
Operating menu
Hauser
169
16.4.5 "Data logging" submenu
Navigation
Diagnostics → Data logging
Assign channel 1 to 4
Navigation
Diagnostics → Data logging → Assign chan. 1 to 4
Description
Allocate a process variable to the respective data logging channel.
Selection
• Off
• Level linearized
• Distance
• Current output 1
• Measured current
• Current output 2
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Factory setting
Off
Additional information
A total of 1000 measured values can be logged. This means:
• 1000 data points if 1 logging channel is used
• 500 data points if 2 logging channels are used
• 333 data points if 3 logging channels are used
• 250 data points if 4 logging channels are used
If the maximum number of data points is reached, the oldest data points in the data log
are cyclically overwritten in such a way that the last 1000, 500, 333 or 250 measured
values are always in the log (ring memory principle).
The logged data are deleted if a new option is selected in this parameter.
Logging interval
Navigation
Diagnostics → Data logging → Logging interval
Description
Define logging interval t
log
.
User entry
1.0 to 3
600.0 s
Factory setting
30.0 s
*
Visibility depends on order options or device settings