Operating menu
Micropilot FMR51, FMR52 HART
132
Hauser
How to enter the table
• Via FieldCare
The table points can be entered via the
Table number (→ 132)
Level (→ 132)
and
parameters. As an alternative, the graphic table editor
may be used: Device Operation → Device Functions → Additional Functions →
Linearization (Online/Offline)
• Via local display
Select the
Edit table
submenu to call up the graphic table editor. The table is displayed
and can be edited line by line.
The factory setting for the level unit is "%". If you want to enter the linearization table
in physical units, you must select the appropriate unit in the
Level unit
parameter
(→ 121) beforehand.
If a decreasing table is entered, the values for 20 mA and 4 mA of the current output
are interchanged. That means: 20 mA refers to the lowest level, whereas 4 mA refers
to the highest level. If required, the current output can be inverted in the
Measuring
mode
parameter.
Table number
Navigation
Setup → Advanced setup → Linearization → Table number
Prerequisite
Linearization type (→ 127)
=
Table
Description
Select table point you are going to enter or change.
User entry
1 to 32
Factory setting
1
Level (Manual)
Navigation
Setup → Advanced setup → Linearization → Level
Prerequisite
•
=
Table
•
Table mode (→ 131)
=
Manual
Description
Enter level value of the table point (value before linearization).
User entry
Signed floating-point number
Factory setting
0 %