Selection
• Foam (>5cm/0,16ft)
• Changing DC values
• Small tanks (< 1m/3ft)
Factory setting
None
Additional information
"Foam (>5cm/0,16ft)" option
This option makes sure that no tank history is used which has been recorded while foam
was present at the surface and thus is no reliable map of the tank property. To achieve
this, the setting
Evaluation mode
=
Long time history
is deactivated.
The
Foam (>5cm/0,16ft)
option is only available for liquid applications (FMR50,
FMR51, FMR52, FMR53, FMR54).
"Changing DC values" option
A tank history which has been recorded with
Evaluation mode
=
Long time history
is
only valid for a fixed dielectric constant. The
Changing DC values
option disables the
setting
Evaluation mode
=
Long time history
and thus avoids wrong measuring values in
the case of a changing dielectric constant.
The
Changing DC values
option is only available for liquid applications (FMR50,
FMR51, FMR52, FMR53, FMR54).
"Small tanks (< 1m/3ft)" option
This option provides a simple possibility to reduce the echo width of the sensor module.
This enables an improved detection of superimposed echos - especially in the near field.
Internally, all paramters related to the echo width are adjusted by this option.
The
Small tanks (< 1m/3ft)
option is only available for liquid measurements with 26
GHz HF module (FMR50, FMR51, FMR52).
Level unit
Navigation
Setup → Advanced setup → Level → Level unit
Description
Select level unit.
Selection
SI units
• %
• m
• mm
US units
• ft
• in
Factory setting
%
Additional information
The level unit may differ from the distance unit defined in the
Distance unit
parameter
(→ 107):
• The unit defined in the
Distance unit
parameter is used for the basic calibration (
Empty
calibration (→ 109)
and
).
• The unit defined in the
Level unit
parameter is used to display the (unlinearized) level.