Liquitrend QMW43
Operation options
Hauser
13
C/Q1
L–
L+
2
1
3
4
f
Q2
I; f
BK
BU
WH
BN
A0041101
8
Connection
Pin 1 Supply v
Pin 2 Current output 4 to 20 mA or frequency 300 to 3
000 Hz
Pin 3 Supply voltage -
Pin 4 IO-Link communication or frequency 300 to 3
000 Hz
6.2
Post-connection check
Are the device and cable undamaged (visual inspection)?
Does the supply voltage match the specifications on the nameplate?
If supply voltage is present, is the green LED lit?
With IO-Link communication: is the green LED flashing?
7
Operation options
7.1
IO-Link information
IO-Link is a point-to-point connection for communication between the device and an IO-
Link master. This requires an IO-Link compatible module (IO-Link master) for operation.
The IO-Link communication interface enables direct access to the process and diagnostic
data. It also provides the option of configuring the device during operation.
The device supports the following characteristics of the physical layer:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition
• SIO mode: Yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 6 ms
• Process data width: 32 bit
• IO-Link data storage: Yes
• Block configuration: Yes
Regardless of the customer-specific default settings selected, the device always has
the option of communicating or being configured via IO-Link.
7.2
IO-Link download
http://www.endress.com/download
• Select "Device Driver" from the list displayed
• In the Type search field, select "IO Device Description (IODD)"
• In the Product Code search field, select the product root
• Click "Search" button → Select result → Download
Optional: In the Text Search search field, enter the device name.